Plan Review Notes
Plan Review Notes For Permit 07010788
Permit Number 07010788
Review Stop P
Sequence Number 2
Notes
Date Text
2007-03-08 09:04:26DENIED 2ND TIME
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 PREVIOUS PLAN REVIEW COMMENTS:
  
 1. OK
  
 2. OK
  
 3.**NO**PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THIS COMMENT WAS NOT ADDRESSED ON THE
 RESUBMITTAL. PLEASE ADDRESS THIS COMMENT ON THE
 RESUBMITTAL.
  
 4.**NO** PER FBC-2004 PLUMBING SECTION 405.3.1 FIXTURE
 CLEARENCES: THERE SHALL BE AT LEAST TWENTY ONE INCHES
 (21") CLEARENCE IN FRONT OF THE WATER CLOSET AND
 LAVATORY TO ANY WALL, FIXTURE OR DOOR.
 NOTE:THIS COMMENT WAS NOT ADDRESSED. PLEASE INDICATE
 THESE MINIMUM CLEARENCES ON THE RESUBMITTED DRAWING.
  
 5.**NO/OK** PER FBC-2004 PLUMBING SECTION 417.4 SHOWER
 COMPARTMENTS: ALL SHOWERS SHALL HAVE A MINIMUM OF 900
 SQUARE INCHEC OF INTERIOR CROSS-SECTIONAL AREA. SHOWER
 COMPARTMENTS SHALL NOT BE LESS THAM 30 INCHES IN
 MINIMUM DIMENSION MEASURED FROM THE FINNISHED INTERIOR
 DIMENSION OF THE COMPARTMENT. PLEASE INDICATE SHOWER
 COMPARTMENT MEASUREMENTS ON THE RESUBMITTED DRAWINGS
 THAT ARE CODE COMPLIANT.
 NOTE: EVEN THOUGH THERE IS AN INDICATION OF 981" SQUARE
 INCHES OF SHOWER SPACE THERE ARE NO CLEAR MEASUREMENTS
 OF THE LENGTH AND WIDTH OF THE SHOWER COMPARTMENT.
 PLEASE CLEARLY INDICATE THESE MEASUREMENTS ON THE
 RESUBMITTAL.
  
 6.**NO** PER FBC-2004 PLUMBING SECTION 417.4.1 WALL
 AREA: THE SHOWER WALLS MUST EXTEND TO A HEIGHT OF 6
 FEET ABOVE THE FLOOR LEVEL OF THE ROOM OR 70 INCHES
 ABOVE THE SHOWER FLOOR AND BE CONSTRUCTED OF SMOOTH,
 NONCORROSIVE AND NONABSORBENT MATERIALS TO PROTECT THE
 BUILDING MATERIALS FROM WATER DAMAGE.
 NOTE: THIS COMMENT WAS NOT ADDRESSED. PLEASE INDICATE
 THIS ON THE RESUBMITAL.
  
 IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved