Plan Review Notes
Plan Review Notes For Permit 07010788
Permit Number 07010788
Review Stop M
Sequence Number 2
Notes
Date Text
2007-03-08 10:45:55*** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-30-07 THE PROPOSED
 BATHROOM WILL NEED A WINDOW OR A EXHAUST FAN, PLEASE
 SHOW ON PLANS.
 ** FROM LAST REVIEW. BATHROOMS, WATER CLOSET
 COMPARTMENTS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH AGGREGATE GLAZING AREA IN WINDOWS OF NOT LESS THAN
 3 SQUARE FEET, ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A MECHANICAL VENTILATION SYSTEM
 ARE PROVIDED. THE MINIMUM VENTILATION RATES SHALL BE 50
 CFM FOR INTERMITTENT VENTILATION OR 20 CFM FOR
 CONTINUOUS VENTILATION. VENTILATION AIR FROM THE SPACE
 SHALL BE EXHAUSTED DIRECTLY TO THE OUTSIDE. PLEASE SHOW
 ON PLANS A WINDOW OR A LIGHT AND FAN, PER 2004 FBC/R
 R303.3.
  
 2) AS NOTED IN LAST REVIEW 1-30-07. THE VALUE ON THE
 PERMIT APPLICATION IS TO LOW, THE VALUE MUST INCLUDE
 ALL LABOR AND MATERIALS AT A FAIR MARKETREPLACEMENT
 COAST. PLEASE ADJUST THE VALUE OR THE BUILDING
 DEPARTMENT WILL NEED TO USING MARSHALL & SWIFT BUILDING
 COST, PER 2004 FBC WPB AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.