| Plan Review Notes For Permit 07010788 |
| Permit Number |
07010788 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-03-05 07:03:35 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | THIS IS THE SAME COMMENT FROM THE PREVIOUS REVIEW AND | | | THERE APPEARS TO BE NO ATTEMPT TO COMPLY. PLEASE SEE | | | F.S. 553.80(2)(B), ATTACHED. | | | | | | 1} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1) NEC 2005. INDICATE | | | COMPLIANCE ON THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS REGARDING THIS ARTICLE, | | | PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|