Plan Review Notes
Plan Review Notes For Permit 07010788
Permit Number 07010788
Review Stop P
Sequence Number 1
Notes
Date Text
2007-01-24 15:39:00DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRE FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106: DRAWINGS
 SUBMITTED IN PENCIL ARE UNACCEPTABLE.
  
 2. PER FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 3. PER FBC-2004 CHAPTER 1 SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
  
 4. PER FBC-2004 PLUMBING SECTION 405.3.1 FIXTURE
 CLEARENCES: THERE SHALL BE AT LEAST 21-INCH CLEARENCE
 IN FRONT OF THE WATER CLOSET AND LAVATORY TO ANY WALL,
 FIXTURE OR DOOR. PLEASE INDICATE THESE MINIMUM
 CLEARENCES ON THE RESUBMITTED DRAWING.
  
 5. PER FBC-2004 PLUMBING SECTION 417.4 SHOWER
 COMPARTMENTS: ALL SHOWERS SHALL HAVE A MINIMUM OF 900
 SQUARE INCHES OF INTERIOR CROSS-SECTIONAL AREA. SHOWER
 COMPARMENTS SHALL NOT BE LESS THAN 30 INCHES IN MINIMUM
 DIMENSION MEASURED FROM THE FINISHED INTERIOR DIMENSION
 OF THE COMPARTMENT. PLEASE INDICATE SHOWER COMPARTMENT
 MEASUREMENTS ON THE RESUBMITTED DRAWINGS THAT ARE CODE
 COMPLANT.
  
 6. PER FBC-2004 PLUMBING SECTION 417.4.1 WALL AREA:
 THE SHOWER WALLS MUST EXTEND TO A HEIGHT OF 6 FEET
 ABOVE THE FLOOR LEVEL OF THE ROOM OR 70 INCHES ABOVE
 THE SHOWER FLOOR AND BE CONSTRUCTED OF SMOOTH,
 NONCORROSIVE AND NONABSORBENT MATERIALS TO PROTECT THE
 BUILDING MATERIALS FROM WATER DAMAGE. PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved