| Plan Review Notes For Permit 07010788 |
| Permit Number |
07010788 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-30 08:24:39 | *** DENIED *** | | | 1) BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER | | | SIMILAR ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING | | | AREA IN WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M | | | 2 ), ONE-HALF OF WHICH MUST BE OPENABLE. EXCEPTION: THE | | | GLAZED AREAS SHALL NOT BE REQUIRED WHERE ARTIFICIAL | | | LIGHT AND A MECHANICAL VENTILATION SYSTEM ARE PROVIDED. | | | THE MINIMUM VENTILATION RATES SHALL BE 50 CFM (23.6 | | | L/S) FOR INTERMITTENT VENTILATION OR 20 CFM (9.4 L/S) | | | FOR CONTINUOUS VENTILATION. VENTILATION AIR FROM THE | | | SPACE SHALL BE EXHAUSTED DIRECTLY TO THE OUTSIDE. | | | PLEASE SHOW ON PLANS A WINDOW OR A LIGHT AND FAN, PER | | | 2004 FBC/R R303.3. | | | | | | 2) THE VALUE ON THE PERMIT APPLICATION IS TO LOW, THE | | | VALUE MUST INCLUDE ALL LABOR AND MATERIALS AT A FAIR | | | MARKETREPLACEMENT COAST. PLEASE ADJUST THE VALUE OR | | | THE BUILDING DEPARTMENT WILL NEED TO USING MARSHALL & | | | SWIFT BUILDING COST, PER 2004 FBC WPB AMEND. 108.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|