2007-01-30 08:24:39*** DENIED ***
 1) BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER
 SIMILAR ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING
 AREA IN WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.279 M
 2 ), ONE-HALF OF WHICH MUST BE OPENABLE. EXCEPTION: THE
 GLAZED AREAS SHALL NOT BE REQUIRED WHERE ARTIFICIAL
 LIGHT AND A MECHANICAL VENTILATION SYSTEM ARE PROVIDED.
 THE MINIMUM VENTILATION RATES SHALL BE 50 CFM (23.6
 L/S) FOR INTERMITTENT VENTILATION OR 20 CFM (9.4 L/S)
 FOR CONTINUOUS VENTILATION. VENTILATION AIR FROM THE
 SPACE SHALL BE EXHAUSTED DIRECTLY TO THE OUTSIDE.
 PLEASE SHOW ON PLANS A WINDOW OR A LIGHT AND FAN, PER
 2004 FBC/R R303.3.
  
 2) THE VALUE ON THE PERMIT APPLICATION IS TO LOW, THE
 VALUE MUST INCLUDE ALL LABOR AND MATERIALS AT A FAIR
 MARKETREPLACEMENT COAST. PLEASE ADJUST THE VALUE OR
 THE BUILDING DEPARTMENT WILL NEED TO USING MARSHALL &
 SWIFT BUILDING COST, PER 2004 FBC WPB AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.