Plan Review Notes
Plan Review Notes For Permit 07010781
Permit Number 07010781
Review Stop B
Sequence Number 1
Notes
Date Text
2007-01-12 18:37:05BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTES.
  
 2- FLAT ROOF SYSTEM:
 A) CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING
 PERMITS. SEE ATTACHED COPY.
  
 B) IF SELECTED SYSTEM IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR
 PERIMETER AND CORNER AREAS NAIL ENHANCEMENT.SEE
 GENERAL LIMITATIONS ON PAGE 19 OF NOA #04-0506.03
 SUBMITTED.
  
 C) IF SELECTED ASSEMBLY HAS MORE THAN ONE BASE SHEET
 FASTENING OPTION, THEN CLEARLY IDENTIFY WHICH OPTION
 WILL BE INSTALLED. SEE CITY POLICY FOR ROOFING
 PERMITS.
  
 D) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT CAN'T BE USED IN THIS AREA
 BECAUSE THE DESIGN PRESSURES ARE TOO LOW FOR THIS AREA
 AND NAIL ENHANCING IS NOT ALLOWED. SEE GENERAL
 LIMITATION #9.
  
 3- IF MECHANICAL EQUIPMENT IS LOCATED ON ROOF, THEN
 PROPER SEPARATE PERMIT IS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712


Account Summary | Usage Policy | Privacy Policy