2007-01-12 17:41:46BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTES.
  
 2- SELECTED ASSEMBLY ON PAGE 32 OF NOA #03-0827.02
 SUBMITTED CAN'T BE INSTALLED IN THIS AREA.ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9 WHICH DOESN'T ALLOW
 NAIL ENHANCING TO INCREASE THE DESIGN PRESSURES OF THE
 ASSEMBLY. SEE GENERAL LIMITATION #9 ON PAGE 40 OF NOA.
  
  
 3. NEED ASSEMBLY WITH GENERAL LIMITATION #7 WHICH
 ALLOWS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS. CALCULATIONS NEED TO BESIGNED AND SEALED BY
 ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT AS
 REQUIRED BY GENERAL LIMITATION #7. SEE PAGE #40.
  
 4- IF SELECTED ASSEMBLY HAVE MORE THAN ONE FASTENING
 OPTION, THEN, CLEARLY IDENTIFY WHICH FASTENING OPTION
 WILL BE INSTALLED. SEE CITY POLICY FOR ROOFING
 PERMITS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER