| 2007-02-14 16:53:15 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 EXISTING BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A-1.1.1 SUBMIT A DETAIL SHOWING COMPLIANCE FOR |
| | THE DRINKING FOUNTAIN PER SECTION 11-4.15 AND ALL |
| | SUBSECTIONS. SHOW COMPLIANCE WITH SECTION |
| | 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE |
| | DIFFICULTY BENDING OR STOOPING. |
| | |
| | 2. SHTS A-1.1.1 & A-4.2.1 FOR THE COMMON USE/PUBLIC |
| | TOILET ROOMS SHOW THE FOLLOWING: |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT (SHOWN AS 9") |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. DISPENSERS |
| | FOR TOILET STALLS |
| | A. 11-4.17.3 EXCEPTION NEW CONST(1)(2) INDICATE |
| | INTERIOR DIMENSIONS OF THE STALLS. (MINIMUM 7'0" WIDTH |
| | REQUIRED). SECTIONS 11-4.1.3(11) & 11-4.1.6(II). SEE |
| | FIGURE 30E. |
| | FOR URINALS |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | FOR LAVS |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | |
| | INDICATE THE W/C TO BE 18" OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE, AND THE LAV TO BE A MINIMUM |
| | OF 15" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. |
| | FIGURES 11-28 & 11-32. |
| | |
| | 3. SHT A-3.1.1 INDICATES A TRASH CHUTE. IF THERE IS |
| | WATER TO A FIXTURE, THEN THERE SHOULD BE A DRAIN. |
| | PLEASE INDICATE IF THERE IS A FLOOR DRAIN IN THE TRASH |
| | ROOM. SECTIONS 301.2 & 301.3. |
| | |
| | 4. SHTS A4.1.0 & A-4.1.1 KEY NOTE LEGEND #7. IN THE |
| | DEMOLITION OF ANY DRAINAGE SYSTEM, DEAD ENDS ARE |
| | PROHIBITED. SECTION 704.5. PLEASE INDICATE ON THE |
| | PLANS. ALL DEMO'D & CAPPED PIPING SHALL BE INSPECTED |
| | PRIOR TO COVERING. |
| | |
| | 5. SHTS A-4.1.2, A-4.1.3, A-4.1.4, A-4.1.5, A-4.1.6 KEY |
| | NOTE #4. IN THE DEMOLITION OF ANY DRAINAGE SYSTEM, DEAD |
| | ENDS ARE PROHIBITED. SECTION 704.5. PLEASE INDICATE ON |
| | THE PLANS. ALL DEMO'D & CAPPED PIPING SHALL BE |
| | INSPECTED PRIOR TO COVERING. |
| | |
| | 6. SHT A-4.2.0 PLEASE INDICATE THE OCCUPANCY & USE FOR |
| | THE BASEMENT. SECTION 302. |
| | |
| | 7. SHT A-4.2.1 FIRST FLOOR TO BE REVIEWED AS A SHELL |
| | ONLY. INDICATE THE PREVIOUS OCCUPANCY AND THE EXPECTED |
| | OCCUPANCY OF THE GROUND FLOOR TO SEE IF CHANGE OF |
| | OCCUPANCY REQUIREMENTS ARE NEEDED.CHAPTER 812. |
| | |
| | 8. SHT A-4.2.1 A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. |
| | |
| | 9. ALL UNITS INDICATE SPECIFICATION "A" OR "B" FOR THE |
| | BATHROOMS. PAGES 7.34 & 7.35. |
| | |
| | 10. SHT A-4.2.2 THRU A-4.2.6 ALL UNITS SHALL COMPLY |
| | WITH FHA-98 DESIGN MANUAL REQUIREMENTS. PLEASE SHOW THE |
| | FOLLOWING FOR EACH UNIT: |
| | A. REINFORCING FOR THE GRAB BARS AT THE TOILET PER |
| | PAGES 6.3, THRU 6.5. |
| | B. INDICATE THE SPACING FOR THE W/C'S PER PAGE 6.7. |
| | C. SHOW THE BACKING FOR THE TUB GRAB BARS PER PAGES 6.8 |
| | & 6.9. |
| | D. SHOW THE MINIMUM CLEAR FLOOR SPACE AT FIXTURES & |
| | APPLIANCES FOR THE KITCHEN. |
| | E. INDICATE THE MINIMUM CLEARANCES BETWEEN COUNTERS |
| | PER PAGES 7.3 THRU 7.8. |
| | F. SHOW THE REQUIREMENTS FOR "U" SHAPED KITCHENS PER |
| | PAGES 7.9 THRU 7.11. |
| | G. SHOW THE REQUIREMENTS FOR THE LAUNDRY EQUIPMENT PER |
| | PAGE 7.19. |
| | H. SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER PAGES |
| | 7.43 THRU 7.46. |
| | I. SHOW THE CLEAR FLOOR SPACE FOR THE LAVS PER PAGES |
| | 7.47 THRU 7.52 |
| | J. SHOW THE CLEAR FLOOR SPACE FOR THE TUBS PER PAGES |
| | 7.53 THRU 7.55. |
| | K. SHOW THE CLEAR FLOOR SPACE FOR THE SHOWER PER PAGES |
| | 7.56 THRU 7.59. |
| | |
| | 11. SHT A-5.2.6 TRASH CHUTE PLAN & GENERAL KEY NOTE #16 |
| | INDICATES A FLUSHING HEAD. BACKFLOW PROTECTION IS |
| | REQUIRED PER SECTION 608.13.5. AN "N-36" TYPE VACUUM |
| | BREAKER IS REQUIRED AT THE HIGH POINT OF THE SUPPLY |
| | LINE. |
| | |
| | 12. SHT P7.1.1 PLEASE INDICATE IF EXISTING PLUMBING |
| | WILL DISCHARGE FROM THE BUILDING SEPARATELY. IF THE |
| | EXISTING FIXTURES ARE CONNECTING TO THE SANITARY |
| | BUILDING DRAIN SHOWN ON THIS SHEET, THEN SHOW THE |
| | PIPING TO ALL FIXTURES, NEW AND EXISTING. TABLES |
| | 710.1(1) & 710.1(2). SOW ALL PIPE SIZES, TRAPS, VENTS, |
| | AND DFU'S. |
| | |
| | 13. SHT P7.1.1 THE FIRST FLOOR SANITARY PLAN INDICATES |
| | 80FU FOR FUTURE RESTURANT. THIS SHALL BE PIPED |
| | SEPARATELY TO A GREASE INTERCEPTOR, A MINIMUM 750 |
| | GALLON AND WILL BE LOCATED OUTSIDE THE BUILDING. THE |
| | OUTLET OF THE GREASE INTERCEPTOR SHALL BE CONNECTED TO |
| | THE SANITARY SEWER. AT THE TIME OF RESTURANT BUILDOUT, |
| | THE CONTRACTOR SHALL CONTACT ENVIRONMENTAL COMPLIANCE |
| | FOR THE SIZING OF THE GREASE INTERCEPTOR. WASTE ORD. |
| | 3434. IF SOME OF THE FIXTURE UNITS ARE FOR NON GREASE |
| | LADEN WASTE, THEN THE SANITARY LINE TO THE RESTAURANT |
| | CAN ACCEPT THE DISCHARGE FROM THOSE FIXTURES. |
| | |
| | 14. SHT P7.1.4 FIRST FLOOR WATER PLAN SHALL INDICATE |
| | WHERE EXISTING RESTROOM FIXTURES CONNECT TO THE WATER |
| | MAIN. SHOW ALL WATER PIPING ON THE FLOOR PLAN AND THE |
| | WATER RISER ISOMETRIC. INDICATE THE LOCATION OF THE |
| | REQUIRED RPZV BACKFLOW. BACKFLOW SHALL BE AT LEAST THE |
| | SAME SIZE AS THE WATER LINE IN WHICH THEY ARE |
| | INSTALLED.SECTION 106.3.5.1.3(3)(8)(10)(13) & TABLE |
| | 603.1(D). |
| | |
| | 15. SHT P7.2.1 SANITARY ISOMETRIC FIRST FLOOR. RECHECK |
| | THE DFU'S & PIPE SIZING PER TABLES 710.1(1) & |
| | 710.1(2). |
| | |
| | 16. SHT P7.2.1 ELECTRIC W/HEATER DETAIL. THERMAL |
| | EXPANSION CONTROL IS REQUIRED PER SECTION 607.3.2. |
| | PLEASE INDICATE METHOD. |
| | |
| | 17. SHT P7.2.2 PLEASE RECHECK THE DFU'S FOR STACK |
| | RISERS A,L,M,N,O,T,V,Q,Z & AB. PER TABLE 709.1 A |
| | BATHROOM GROUP IS 5FU. THIS INCLUDES A WATER CLOSET, |
| | TUB OR SHOWER, BIDET & 1 LAV. ADDITIONAL LAVS ARE 1FU |
| | WHERE APPLICABLE. MOST BATHROOMS ARE 5FU AND THE |
| | BATHROOMS WITH AN EXTRA LAV ARE 6FU. IF THE EXISTING |
| | FIXTURES ARE CONNECTING TO THE BUILDING SANITARY DRAIN |
| | ON THIS SHEET, PLEASE SHOW ALL PIPES FOR THE EXISTING |
| | FIXTURES CONNECTING TO THE BUILDING DRAIN AND ADD BTU'S |
| | TO SYSTEM. SECTION 106.1.1 & TABLES 710.1(1) 710.1(2). |
| | |
| | 18. SHT P7.2.2 NO "Y" SANITARY RISER DIAGRAM HAS BEEN |
| | SUBMITTED. THIS RISER IS INDICATED ON THE FLOOR PLAN |
| | AND THE BUILDING SANITARY DRAIN ISOMETRIC. PLEASE |
| | SUBMIT A "Y" RISER SHOWING ALL PIPE SIZES, TRAPS, VENTS |
| | ETC. SECTION 106.3.5.1.3(4)(6)(13). |
| | |
| | 19. SUBMIT AN EMERGENCY PAN DRAIN BUILDING DRAIN LINE |
| | ISOMETRIC FOR THE WATER HEATERS. SHOW ALL PIPE SIZES, & |
| | INDICATE THE TERMINATION POINT OF THE DRAIN LINE. |
| | SUBMIT RISER DIAGRAM ISOMETRICS FOR THE PAN DRAIN |
| | LINES. SECTION 106.3.5.1.3(13). |
| | |
| | 20. SHT P7.2.3 WATER ISOMETRIC FOR THE 2ND THRU 6TH |
| | FLOORS UNITS 03 & 04. FULL OPEN VALVES ARE REQUIRED ON |
| | THE TOP OF ALL WATER DOWN-FEED LINES. SECTION |
| | 606.1(4). |
| | |
| | |
| | 21. SHT P7.2.3 WATER ISOMETRIC FOR THE 1ST FLOOR. |
| | INDICATE ALL FIXTURES, INCLUDING THE EXISTING ON THE |
| | WATER RISER DIAGRAM. SHOW ALL PIPE SIZES, VALVES, AND |
| | WATER HAMMER ARRESTORS, (AS REQUIRED BY SECTION 604.9). |
| | SHOW ALL THE FIXTURES CONNECTING TO THE WATER MAIN AT |
| | THAT FLOOR LEVEL. SECTION 106.1.1. |
| | |
| | 22. ALL PLUMBING, ELECTRICAL & MECHANICAL SHEETS. THE |
| | ADDRESS FOR THE PROFESSIONAL ENGINEERING BUSINESS ON |
| | THE TITLE BLOCKS DOES NOT REFLECT THE ADDRESS OF RECORD |
| | FROM THE DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE |
| | INDICATE CORRECT ADDRESS OR HAVE THE DBPR WEBSITE |
| | UPDATED WITH THE CORRECT ADDRESS. FAC 61G15-23.002(2) & |
| | FS 471.025 |
| | |