| 2007-02-27 16:17:27 | *****DENIED***** |
| | |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 03.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT HINDER OR INTERFERE WITH ACCESS TO THE PROPERTY OR |
| | THE VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 04.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE |
| | BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF |
| | WORK.IF SO, THIS WILL BE PERMITTED ONLY WHERE |
| | REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION |
| | FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE |
| | ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ |
| | ARE IN PLACE. |
| | |
| | 05.ALL FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 06.PLEASE LIST THE FIRE RATING FOR THE DOORS LEADING |
| | TO THE STAIR TOWERS (MARKED AS 2). |
| | |
| | 07.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS ON THE BUILDING.AS PER WEST PALM |
| | BEACH CODE, THOSE NUMBERS SHALL BE NO LESS THAN 6" IN |
| | HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 08.PLEASE INDICATE THE INTERIOR FINISH |
| | CLASSIFICATIONS FOR THE WALLS AND CEILINGS FOR THE |
| | EXITS, EXIT ACCESS CORRIDORS, AND OTHER SPACES. |
| | |
| | 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING THE |
| | TRAVEL DISTANCE TO THE EXITS.THE LOCATION OF THE |
| | 2A:10BC RATED FIRE EXTINGUISHERS (SATISFYING THE 75 |
| | FEET TRAVEL DISTANCE) AND SMOKE ALARMS MAY ALSO BE |
| | INCLUDED. |
| | |
| | 10.IT IS NOTED THAT THIS BUILDING IS SPRINKLERED, |
| | PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM. |
| | SHOULD THERE BE A MODIFICATION TO THIS SYSTEM DUE TO |
| | THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED. |
| | |
| | 11.IT IS ASSUMED THAT THIS BUILDING HAS A FIRE ALARM |
| | SYSTEM, PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM |
| | SYSTEM.SHOULD THERE BE A MODIFICATION TO THIS SYSTEM |
| | DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED. |
| | |
| | 12.PLEASE PROVIDE PRESCRIPTIVE STRENGHT REQUIREMENTS |
| | FOR ALL THE GUARDRAILS AND HANDRAILS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE (ON THE PLAN) EACH COMMENT |
| | WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |