| Date |
Text |
| 2007-01-30 16:51:49 | **** UNSAT **** |
| | |
| | *** IMPORTANT*** |
| | * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND |
| | PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE |
| | RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE |
| | WHICH WERE NOT MADE ON THIS REVIEW. |
| | ** PLEASE ALSO KNOW THAT THIS IS A CHANGE IN OCCUPANCY |
| | WHICH WILL REQUIRE TECHNICAL CODE COMPLIANCE FOR THE |
| | CURRENT CODES AND WELL AS OTHER REQUIREMENTS FOR CODE |
| | COMPLIANCE FOR BUILDING, FIRE ETC. |
| | THERE ARE A SUBSTANTIAL AMOUNT OF ITEMS WHICH CAN NOT |
| | BE REVIEWED AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| | CORRECT. |
| | PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| | OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER |
| | 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO |
| | THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL, |
| | PLUMBING BUILDING ETC. |
| | PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| | ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| | COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM. |
| | 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-20, 2003 |
| | NFPA-101, 2003 NFPA-1. |
| | |
| | ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| | ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL |
| | REVIEW ONLY. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS |
| | SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS, |
| | STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC |
| | 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE |
| | THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH |
| | PLANS. |
| | PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE |
| | INDICATED. |
| | PLEASE SEE NO FIRE ALARM PLANS AND FIRE SPRINKLER PLANS |
| | WERE SUBMITTED WHICH WILL BE REQUIRED FOR THE BASE |
| | BUILDING PROTECTION AND IS REQUIRED TO BE SUBMITTED |
| | WITH MAIN BUILDING PLANS FOR REVIEW OF THESE REQUIRED |
| | ITEMS |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE COMMENTS POSSIBLY FROM ZONING AND |
| | BUILDING REVIEW WITH RESPECT TO PARKING AND REQUIRED |
| | MINIMUM LIGHTING LEVELS AND LOCATIONS OF PARKING. |
| | ZONING MAY COMMENT BASED ON DIVISION 4, DMP 86294. (NOT |
| | AN ELECTRICAL REQUIREMENT, HOWEVER WILL AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION |
| | FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE |
| | INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE |
| | PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT |
| | THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON |
| | PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS |
| | IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE |
| | MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A |
| | *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON |
| | PLANS. |
| | PLEASE BE SURE TO INCLUDE ANY LIGHTING CIRCUITING FROM |
| | HOUSE PANELS ETC. |
| | PLEASE KNOW THAT ANY PARKING ACROSS THE STREET WHICH IS |
| | LOCATED ON ANOTHER LEGAL PROPERTY MAY NOT BE FED FROM |
| | THIS BUILDING ELECTRICAL SERVICE. |
| | ** PLEASE SEE FBC 2004. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND |
| | PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE. |
| | PLEASE SEE ALL AREAS FOR COMMON AREAS WHICH ARE NOT |
| | PART OF THE RESIDENTIAL SHALL BE SHOWN AND COMPLY WITH |
| | THE 2006 REVISIONS TO THE 2004 FBC CHAPTER 13.PLEASE |
| | SEE 13-415.1.AB.1 AND 13-415.2. |
| | PLEASE SEE THAT ALL ELECTRICAL AS SHOWN ON PLANS SHALL |
| | BE INCLUDED IN THE ENERGY CALCULATIONS AS WELL AS THE |
| | ELECTRICAL IN ENERGY CALCULATIONS NEEDS TO BE SHOWN ON |
| | PLANS.(PLEASE SEE ELEC ON CALCS NOT ON PLANS) |
| | PLEASE SEE ALL RESIDENTIAL AREAS ARE STILL FIGURED INTO |
| | ENERGY CALCULATIONS EVEN IF THOSE AREAS ARE EXEMPT FROM |
| | AUTOMATED CONTROL DEVICES. |
| | * PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, |
| | BY THE ENGINEER OF RECORD. 13-103.1.1.1 |
| | |
| | 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED |
| | FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC |
| | 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE ALL COMMON AREAS AND SEPARATE SPACES |
| | CONTAINING FLOOR TO CEILING HEIGHT PARTITIONS. PLEASE |
| | SEE THIS INCLUDES ALL FLOORS AND LEVELS. |
| | |
| | 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM |
| | FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22, |
| | 620.23, 620.24 AND 620.51. |
| | PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM |
| | AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT |
| | FEED ANY OTHER AREAS. PLEASE SEE PLANSDO NOT INDICATE |
| | THESE CIRCUITS AT THIS TIME AND AS COMPLETE CODE |
| | COMPLIANCE FOR ELEVATOR ROOMS, CONTROLS, DETECTION |
| | DEVICES ETC WILL BE REQUIRED TO THE MEET THE CURRENT |
| | CODE IF NOT ALREADY. |
| | PLEASE ALSO SEE THE STATE ELEVATOR CODE. |
| | PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR |
| | MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11, |
| | 620.12 ETC. |
| | |
| | 9) NOTE:PLEASE SEE MISSING CIRCUITING ON SOME COMMON |
| | AREAS ELECTRICAL FIXTURES AND DEVICES. PLEASE COMPLETE |
| | ALL CIRCUITING ON PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULE(S). |
| | PLEASE SEE COMMENTS LATER WITH RESPECT TO MANY PANEL |
| | SCHEDULES WHICH WERE NOT SUBMITTED FOR REVIEW. |
| | 408.4, 310.16,ETC |
| | PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY AND EXIT |
| | LIGHTS. |
| | |
| | 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND. |
| | PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS |
| | TIME. |
| | FBC 106.1.2. |
| | |
| | 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| | LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, AND |
| | ELECTRICAL EQUIPMENT ROOMS. PLEASE SEE OTHER ROOMS FOR |
| | GENERATOR, FIRE PUMP ETC WILL ALSO REQUIRE THIS , |
| | HOWEVER PLEASE SEE OTHER COMMENTS FOR RELOCATION OF |
| | THESE WHICH WILL AFFECT THE LOCATIONS. |
| | NFPA-101 7.8, 7.9 |
| | NFPA-70 700.16, AND 700.12E. |
| | |
| | 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR |
| | ALL EGRESS PATHS. |
| | PLEASE SHOW COMPLETED ELECTRICAL PLANS FOR ALL EGRESS |
| | STAIRS AND PATHS. PLEASE SHOW ALL EXISTING MEETING THE |
| | CURRENT CODES OR NEW TO BE INSTALLED. PLEASE SEE |
| | CIRCUITING AND TYPE OF FIXTURES ARE ALSO REQUIRED. |
| | PLEASE SEE MINIMUM LEVELS UNDER NORMAL AND UNDER |
| | EMERGENCY ARE REQUIRED FOR ALL EGRESS PATHS. THIS WOULD |
| | INCLUDE ANY EGRESS FROM BASEMENT TO PUBLIC RIGHT OF WAY |
| | AND EGRESS OUT OF BUILDING TO PUBLIC RIGHT OF WAY. |
| | PLEASE SEE ANY STAIR AREAS OUTSIDE WHICH HAS NOT PLACED |
| | THE OCCUPANT TO THE PUBLIC RIGHT OF WAY WILL REQUIRE |
| | EMERGENCY ILLUMINATION AT THESE LOCATIONS. PLEASE SEE |
| | NFPA-101 7.8.1.3, 7.9.2.2. |
| | |
| | 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE |
| | AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| | BE REVIEWED FOR CODE COMPLIANCE. PLEASE KNOW COMPLETE |
| | CODE COMPLIANCE MUST BE MET. PLEASE SEE THERE ARE PANEL |
| | SCHEDULES FOR NEW PANELS WHICH WERE NOT SUBMITTED OR |
| | SHOWN. PLEASE SUBMIT ALL INFORMATION FOR EXISTING |
| | SERVICE AND WHAT ALL THIS EXISTING EQUIPMENT IS |
| | FEEDING. PLEASE BE SURE TO SEE COMMENTS WITH RESPECT TO |
| | FIRE PUMP AND EPSS. |
| | PLEASE SEE RISER SHOWS A NEW MDP ALSO, HOWEVER NOT |
| | PANEL SCHEDULE WAS SUBMITTED OR SHOWN. PLEASE SEE OTHER |
| | ELECTRICAL PANELS FOR FUTURE USE WERE NOT SUBMITTED. |
| | PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| | ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| | SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| | RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| | ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| | 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| | 110.26 ETC. |
| | PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| | |
| | 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY |
| | 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2. |
| | PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED |
| | FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM |
| | CONTROL PANEL. |
| | ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| | SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| | PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| | NOT ACCEPTABLE TO THIS AHJ. |
| | 110.3, 90.4. |
| | |
| | 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN |
| | THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THAT |
| | NO LOAD CALCULATIONS WERE SUBMITTED FOR NEW SERVICE OR |
| | ANY EXISTING. PLEASE INDICATE LOAD SUMMARY FOR ALL OF |
| | THE SERVICES AND HOW THESE SIZES WERE DERIVED. |
| | PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR |
| | CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| | NOT BE DETERMINED AT THIS TIME. |
| | PLEASE SEE ALL OF 220.(THERE ARE TOO MANY SECTIONS TO |
| | LIST) |
| | PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| | LOADS AND LARGEST MOTORS LOADS AT 125%. |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| | |
| | 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE |
| | AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE |
| | CORRELATE WITH THE DIVISION SPEC SUBMITTED. |
| | 106.1.2. |
| | NEC 110.9 |
| | |
| | 18) NOTE: PLEASE SEE 240.21C6 FOR MAIN DISCONNECTS OR |
| | MAIN CIRCUIT BREAKERS REQUIRED ON THE SECONDARY SIDE OF |
| | THE TRANSFORMERS CAN NOT BE VERIFIED AT THIS TIME. |
| | PLEASE ALSO SEE 408.36 |
| | |
| | 19) NOTE: PLEASE SEE NFPA-110 2002 CHAPTER 7 FOR |
| | COMPLIANCE FOR THE EPSS/ EMERGENCY GENERATOR. PLEASE |
| | SEE THERE ARE MANY ITEMS TO BE VERIFIED FOR BRING |
| | EXISTING UP TO CODE. |
| | A) PLEASE SEE 7.3.3 WHICH REQUIRES A MINIMUM OF 30FT |
| | CANDLES FOR ROOM. (ALSO PREVIOUS NOTE ABOVE FOR EM |
| | BATTERY BACK UP LIGHTING REQUIRED. |
| | B) PLEASE SEE THE LOCATION OF THE GENERATOR DOES NOT |
| | APPEAR IT CAN BE LOCATED IN THE BASEMENT BASED ON THE |
| | ELEVATION. PLEASE SEE 7.2.3* |
| | PLEASE SEE SOME OFTHE FOLLOWING TEXT IS EXTRACTED |
| | FROM THE CODE. |
| | |
| | A.7.2.3 EPSS EQUIPMENT SHOULD BE LOCATED ABOVE KNOWN |
| | PREVIOUS FLOODING ELEVATIONS WHERE POSSIBLE. |
| | A.7.2.4 WHEN INSTALLING THE EPSS EQUIPMENT AND RELATED |
| | AUXILIARIES, ENVIRONMENTAL CONSIDERATIONS SHOULD BE |
| | GIVEN, PARTICULARLY WITH REGARD TO THE INSTALLATION OF |
| | THE FUEL TANKS AND EXHAUST LINES, OR THE EPS BUILDING, |
| | OR BOTH. |
| | TO PROTECT AGAINST DISRUPTION OF POWER IN THE FACILITY, |
| | IT IS RECOMMENDED THAT THE TRANSFER SWITCH BE LOCATED |
| | AS CLOSE TO THE LOAD AS POSSIBLE. THE FOLLOWING ARE |
| | EXAMPLES OF EXTERNAL INFLUENCES: |
| | (1)NATURAL CONDITIONS |
| | (A)STORMS |
| | (B)FLOODS |
| | (C)EARTHQUAKES |
| | (D)TORNADOES |
| | (E)HURRICANES |
| | (F)LIGHTNING |
| | (G)ICE STORMS |
| | (H)WIND |
| | (I)FIRE |
| | (2)HUMAN-CAUSED CONDITIONS |
| | (A)VANDALISM |
| | (B)SABOTAGE |
| | (C)OTHER SIMILAR OCCURRENCES |
| | (3)MATERIAL AND EQUIPMENT FAILURES |
| | FOR NATURAL CONDITIONS, EPSS DESIGN SHOULD CONSIDER THE |
| | "100-YEAR STORM" FLOODING LEVEL OR THE FLOODING LEVEL |
| | PREDICTED BY THE SLOSH MODELS FOR A CLASS 4 HURRICANE. |
| | SLOSH STANDS FOR SEA, LAKE, OVERLAND, SURGES BY |
| | HURRICANES. |
| | |
| | THE ROOMS, SHELTERS, OR SEPARATE BUILDINGS HOUSING |
| | LEVEL 1 OR LEVEL 2 EPSS EQUIPMENT SHALL BE DESIGNED AND |
| | LOCATED TO MINIMIZE THE DAMAGE FROM FLOODING, INCLUDING |
| | THAT CAUSED BY THE FOLLOWING: |
| | (1)FLOODING RESULTING FROM FIRE FIGHTING |
| | (2)SEWER WATER BACKUP |
| | (3)SIMILAR DISASTERS OR OCCURRENCES |
| | |
| | C) PLEASE SEE THE MINIMUM CLEARANCE FOR ATS SWITCHES |
| | CAN NOT BE VERIFIED AT THIS TIME. |
| | D) PLEASE SEE 7.9.1 FOR FUEL SYSTEM REQUIREMENTS AS |
| | WELL AS NFPA-20 2003 SECTION 9.6.2.2 THE FUEL SUPPLY |
| | CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS OF FIRE |
| | PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP |
| | CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER |
| | DEMANDS. |
| | E) PLEASE SEE MANY ITEMS FOR THE EXISTING EMERGENCY |
| | SYSTEM CAN NOT BE VERIFIED. THE INFORMATION WHICH NEEDS |
| | TO BE SHOWN NEEDS TO BE PLACED ON PLANS AS IF THIS WAS |
| | A NEW BUILDING BEING CONSTRUCTED UNDER THE CURRENT |
| | CODES FOR THE ELECTRICAL AND EMERGENCY SYSTEMS. (EVEN |
| | IF SHOWN AS EXISTING MEETING THE CURRENT CODE). |
| | |
| | 20) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE |
| | OF WORK WILL NEED TO BE ADJUSTED ONCE ALL REVIEWS ARE |
| | DONE AND PLANS ARE BROUGHT UP TO CODE. |
| | PLEASE SEE FBC 108.3 ADMIN SECTION. |
| | |
| | 21) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE(S) |
| | SHALL BE SPECIFIC TO ALL AREAS/ROOMS AND SPACES IN |
| | WHICH THEY FEED. PLEASE SEE THE COMMENTARY SECTION OF |
| | THE 2005 NEC WHICH EXPLAINS THIS.PLEASE SEE THE |
| | REQUIREMENT THAT THE IDENTIFICATION FOR EVERY CIRCUIT |
| | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND |
| | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE |
| | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE |
| | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, |
| | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN |
| | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. |
| | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH |
| | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE |
| | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING |
| | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP |
| | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES |
| | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR |
| | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL |
| | REQUIRED BY THIS SECTION. |
| | PLEASE BE SURE TO CORRELATE PLANS AND CIRCUITING SHOWN |
| | AT THIS TIME. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | 22) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 |
| | WHICH ARE REQUIRED FOR WALLS 2FT OR GREATER AND WITHIN |
| | 6FT OF ANY DOOR OPENINGS. |
| | |
| | 23) NOTE: PLEASE SEE LOCATION OF BATHROOM GFI |
| | RECEPTACLES WHICH ARE REQUIRED TO BE WITHIN 3FT OF THE |
| | LAVATORIES EDGE; HOWEVER MAY NOT CROSS OVER ONE |
| | LAVATORY TO UTILIZE THE RECEPT. |
| | PLEASE SEE THIS CAN BE CORRECTED BY PLACING AN |
| | ADDITIONAL GFI ON PLANS OR RELOCATING THE ONE ALREADY |
| | SHOWN TO BE LOCATED IN BETWEEN THE TWO LAVS. |
| | 210.52D |
| | |
| | 24) NOTE: PLEASE CLARIFY IF THIS BUILDING IS STILL |
| | ADJOINED TO THE BUILDING ACROSS THE ALLEY ON THE SOUTH |
| | SIDE. |
| | PLEASE SEE THIS MAY AFFECT USE ETC. |
| | |
| | 25) NOTE: PLEASE INCLUDE ALL FIRE RATINGS FOR EXISTING |
| | FPL VAULT WALLS. |
| | PLEASE SEE BUILDING CODE REQUIREMENTS AS WELL AS NEC |
| | 450. |
| | |
| | 26) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM SIZE OF OVER |
| | CURRENT PROTECTION OF TRANSFORMER UNLESS MEETING NOTE |
| | #3 IS 125%. |
| | |
| | 27) NOTE: PLEASE SEE GROUNDING ELECTRODE RISER AND |
| | NOTES AS THIS STATES FOOTER STEEL TO BE PART OF THE |
| | GROUNDING ELECTRODE SYSTEM. PLEASE KNOW AS THIS IS AN |
| | EXISTING BUILDING AND NOT NEW, THE EXISTING FOOTER (IF |
| | THEY CONTAINED STEEL) ARE NOT REQUIRED TO HAVE THE |
| | ATTACHMENT MADE AS THE CUTTING/CHIPPING INTO AN |
| | EXISTING FOOTER OF THIS AGE WOULD AFFECT THE STRUCTURAL |
| | INTEGRITY OF THE FOOTER. PLEASE KNOW THAT THIS IS |
| | PERMITTED HOWEVER NOT REQUIRED. IF SHOWN ON RISER THEN |
| | THIS WILL BE REQUIRED. PLEASE KNOW THAT ANY STRUCTURAL |
| | BUILDING STEEL WOULD BE REQUIRED. |
| | PLEASE SEE 250.50 |
| | |
| | 28) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM |
| | DOES NOT SEEM TO INCLUDE ANY CONNECTION TO THE FIRE |
| | SPRINKLER PIPE(S) AS REQUIRED. 250.50, 250.104 EXISTING |
| | OR NEW? |
| | |
| | 29) NOTE: PLEASE CLARIFY THE DUPLEX WHICH IS A |
| | HALF/SWITCHED RECEPTACLE FOR THE DISPOSAL SHOWN ON |
| | PLANS. PLEASE KNOW THAT IF THIS DEVICE IS NOT GOING TO |
| | FEED BOTH THE DISHWASHER AND DISPOSAL AS TYPICALLY |
| | DONE, THEN THIS WOULD BE REQUIRED TO BE A SINGLE |
| | RECEPTACLE DEVICE NOT A DUPLEX. |
| | PLEASE KNOW THAT IF INDEED THIS DUPLEX IS GOING TO FEED |
| | BOTH THE DISPOSAL AND DISHWASHER THEN A 2-POLE CIRCUIT |
| | BREAKER IS REQUIRED AND CORRECTION OF PANEL SCHEDULE |
| | WILL NEED TO BE MADE. |
| | PLEASE SEE 210.3, 210.4, 210.7, 210.21, 210.23 ETC. |
| | |
| | 30) NOTE: PLEASE SEE LOAD CALCULATIONS FOR UNITS ARE TO |
| | BE DONE PER NEC 220.82/220.84. PLEASE SEE THAT AS THIS |
| | IS NOT AN EXISTING UNIT, HOW IS THE FIRST 8KVA BEING |
| | INDICATED AT 100%? PLEASE SEE THIS WOULD BE THE FIRST |
| | 10KAV FOR NEW CONSTRUCTION. |
| | |
| | 31) NOTE: PLEASE CLARIFY ALL TRANSFORMERS BEING SHOWN |
| | ON SITE PLANS. ARE THESE ALL FEEDING THIS BUILDING? |
| | |
| | 32) NOTE: PLEASE SEE RISER AS SHOWN DOES NOT INCLUDE |
| | ANY METERING DEVICES FOR THE ELECTRICAL FEEDING |
| | COMMERCIAL SPACES EITHER BY WAY OF CT OR METER CAN? |
| | PLEASE SEE FPL SERVICE GUIDELINES AS THIS IS REQUIRED |
| | TO BE INDICATED ON ELECTRICAL PLANS AT THIS TIME. |
| | PLEASE |
| | |
| | 33) NOTE: PLEASE PROVIDE COMPLETE INFORMATION FOR FIRE |
| | PUMP, FIRE PUMP CONTROLLER AND ALL ASSOCIATE |
| | EQUIPMENT. |
| | PLEASE SEE THE FIRE PUMP RISER AS SHOWN AND HOW |
| | EQUIPMENT IS BEING FED FROM THE HOUSE SERVICE IS NOT |
| | PERMITTED. PLEASE SEE RISER ALSO SHOWS THIS BEING FED |
| | FROM OTHER SEPARATE SERVICE ALSO. |
| | PLEASE SEE 2005NEC 695 AND 2003 NFPA-20 (ALL). |
| | PLEASE INDICATE IF THESE ARE NEW TO BE INSTALLED OR |
| | EXISTING WHICH MEETS CURRENT CODES. |
| | PLEASE SEE THE LOCATIONS OF THE FIRE PUMP ETC NEEDS TO |
| | BE LOCATED PER CODES GIVEN AS NOTED. |
| | ** AS SHOWN CODE COMPLIANCE IS NOT ACHIEVED. |
| | |
| | 34) NOTE: PLEASE SEE 240.24, 110.26 AND 408.17 FOR |
| | LOCATIONS OF OVER CURRENT PROTECTION IN STORAGE AREAS. |
| | |
| | PLEASE SEE AIR HANDLER UNITS WHICH IS BEING SHOWN IN |
| | STORAGE CLOSETS WHICH IS NOT PERMITTED. |
| | |
| | 35) NOTE: PLEASE SEE ONE SET CONTAINING REPEATED |
| | SHEETS. |
| | PLEASE SUBMIT TWO COMPLETE SETS OF PLANS. PLEASE KNOW |
| | BASED ON SCOPE OF WORK, VALUE, CONSTRUCTION, AND THE |
| | SIZE OF THE EXISTING BUILDING ALONG WITH OTHER |
| | CONSIDERATIONS, THIS MAY REQUIRE AN ON-SITE INSPECTOR? |
| | IF THIS IS THE CASE, THEN THREE SETS OF SIGNED, DATED |
| | AND SEALED PLANS WILL BE REQUIRED. |
| | 109.3.6, 106.1.2, 106.3.5.1.2 |
| | |
| | 36) NOTE: PLEASE SEE 109.3.6.4.4 |
| | PLANS WHICH ARE SIGNED, DATED AND SEALED BY AN |
| | ARCHITECT OR ENGINEER SHALL CONTAIN A STATEMENT THAT: * |
| | TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER (FLORIDA |
| | STATUTES) 633. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES FOR ALL TRADES/TITLE SHEETS FOR EACH TRADE |
| | AND/OR TITLE BLOCKS. |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-30 08:35:29 | IN ELEC FOR REVIEW |