| 2007-01-30 18:39:36 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE THE CODE CITED ON PLANS FOR THE |
| | NFPA-70 SHOULD READ THE 2005. PLEASE KNOW THAT THE |
| | STATE OF FLORIDA ADOPTED THE 2005 NEC ON DECEMBER 8TH, |
| | 2006. |
| | PLEASE ALSO STATE THE 2006 REVISIONS TO THE 2004 FBC |
| | WHICH ALSO CHANGED ON THAT DATE. |
| | |
| | 2) NOTE: PLEASE PROVIDE THE CORRECT VALUE AMOUNT FOR |
| | THE SCOPE OF WORK WHICH SHALL INCLUDE ALL LABOR AND |
| | MATERIALS EVEN IF ANY EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 108.3 |
| | THIS COMMENT HAS BEEN MADE ON EVERY OTHER PROJECT |
| | SUBMITTED FOR PERMIT IN THE CITY OF WEST PALM BEACH AND |
| | YET THE PERMIT APPLICATIONS ARE STILL BEING SUBMITTED |
| | WITH LOW VALUES. |
| | PLEASE KNOW AS THIS A LEGAL DOCUMENT SIGNED BY THE |
| | CONTRACTOR LICENSED UNDER FS 468, THE APPLICATIONS ARE |
| | BEING RETAINED IN FILES FOR POSSIBLE REVIEW BY THE |
| | STATE CONTRACTORS LICENSING BOARD. |
| | PLEASE PLACE THE CORRECTED VALUES ON APPLICATIONS |
| | BEFORE PERMITS ARE APPLIED FOR. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |