| 2007-02-23 11:30:28 | BUILDING PLAN REVIEW |
| | PERMIT: 07010762 |
| | ADD: 1750 FLORIDA MANGO RD |
| | CONT: OPTIMAL ELECTRIC |
| | TEL: (407)323-5321 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) SHEET E-2 INDICATES THIS LOCATION IS IN A "B" FLOOD |
| | ZONE, PLEASE CORRECT TO |
| | FLOOD ZONE A-9, MINIMUM FLOOD ELEVATION FOR FINISH SLAB |
| | IS 13'-6". |
| | |
| | 3) SHEET S-2 FOUNDATION NOTE# 10 INDICATES TESTING FOR |
| | THE MINIMUM SAFE BEARING VALUE OF THE SOIL. FBC |
| | 1802.2.1 QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 4)SHEET S-2 WIND DESIGN CRITERIA, PLEASE CORRECT THE |
| | IMPORTANCE FACTOR, |
| | ASCE 7-02 TABLE 1-1DESIGNATED EMERGENCY PREPAREDNESS, |
| | COMMUNICATIONS AND OPERATING CENTERS AND OTHER |
| | FACILITIES REQUIRED FOR EMERGENCY RESPONSE. |
| | CATEGORY IV/TABLE 6-1- IV=1.5 |
| | |
| | 5) VALUE FOR THE SCOPE OF WORK TO INCLUDE MATERIALS AND |
| | LABOR. THE VALUE OF THIS PROJECT IS UNDER THE COST OF |
| | THE GENERATOR ITSELF. |
| | 108.3*BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE |
| | CONGRESS. |
| | |