| Plan Review Notes For Permit 07010761 |
| Permit Number |
07010761 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-02-16 17:52:44 | BUILDING REVIEW 4TH CHECKLIST: | | | | | | 1- ENGINEER CALCULATIONS: | | | A) ENGINEER REVISED LETTER STATES THAT"NAIL | | | SPACING OF 9"O.C. INACCORDANCE WITH THE NOA WORKS | | | EXCEPT IN THE CORNER WHERE THE SPACING NEEDS TO BE | | | REDUCED TO 5"O.C.".CALCULATED DESIGN PRESSUREAT | | | PERIMETER AREAIS-59.2PSF.ACCORDING TO PAGE 17 OF | | | NOA 02-0212.07 SUBMITTED THE MAXIMUM DESIGN PRESSURE | | | USING 11GA RING SHANK NAILS IS -52.5. THEREFORE,ALSO | | | NEEDSNAIL ENHANCING AS ALLOWED BY GENERAL LIMITATION | | | #7.REVISE AS REQUIRED. | | | | | | B) ENGINEER TO REVISEBASE SHEET FASTENER SPACING | | | CALCULATIONS ON LAST PAGE OF CALCULATIONS SUBMITTED. | | | ACCORDING TO RAS 117 CALCULATIONS SEC. 8.1 THE MAXIMUM | | | DESIGN PRESSURES FOR THE ACCEPTED ASSEMBLY ARE THE ONES | | | APPLICABLE TO THE ROOF AREA (1).REVISE FASTENER | | | SPACING FOR ZONE 1 AS REQUIRED. | | | | | | C) ENGINEER TO SEE ATTACHED COPY OF FLORIDA STATUTE | | | REGARDING DESIGN PROFESSIONAL DOCUMENTS AND PLAN REVIEW | | | FEES. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|