| Plan Review Notes For Permit 07010761 |
| Permit Number |
07010761 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-02-12 18:06:42 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- ENGINEERING CALCULATIONS SUBMITTED: | | | A) FASTENER SPACING CALCULATIONS ARE WRONG. ENGINEER | | | USED ANCHOR SPACING RN AND RS IN THE EQUATION ON LAST | | | PAGE OF CALCULATIONS SUBMITTED.RAS 117 GENERAL | | | EQUATION10.4.5 CALLS FOR ROW SPACING, NOT ANCHOR | | | SPACING.NEED TO REVISE CALCULATIONS AS REQUIRED. | | | | | | B) ENGINEER USED 20SF AS THE TRIBUTARY AREA FOR THE | | | DESIGN PRESSURES CALCULATIONS. NEED TO USE AT LEAT THE | | | 10SF TRIBUTARY AREA . THE EFFECTIVE WIND AREA SHALL NOT | | | BE GREATERTHAN THE AREA THAT IS TRIBUTARY TO AN | | | INDIVIDUAL FASTENER. SEE EFFECTIVE WIND AREA DEFINITION | | | IN CHAPTER 16 FBC 2004. | | | | | | C) ENGINEER TO REVISE ALL FBC TABLES REFERENCED IN | | | THE CALCULATIONS. NEED TO SEE REVISED FBC PAGES (BLUE | | | PAGES) AND REVISE TABLES AS REQUIRED. | | | | | | D) ONLY THE DESIGN PRESSURES FOR ROOF ARE REQUIRED. | | | THE REST OF THE DESIGN PRESSURES ARE NOT REQUIRED FOR A | | | ROOF PERMIT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|