| Plan Review Notes For Permit 07010761 |
| Permit Number |
07010761 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-12 16:45:55 | BUILDING REVIEW CHECKLIST: | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTES. | | | | | | 2- FLAT ROOF SYSTEM; | | | A) SPECIFY BASE SHEET FASTENING OPTION AS REQUIRED | | | BY CITY POLICY FOR ROOFING PERMITS. SEE ATTACHED COPY. | | | | | | B) GENERAL LIMITATION #7 CALLS FOR RAS 117 | | | CALCULATIONS TO BE SIGNED AND SEALED BY ARCHITECT, | | | ENGINEER OR REGISTERED ROOFING CONSULTANT. PROVIDE SUCH | | | INFORMATION. SEE GENERAL LIMITATION #7 ON PAGE 20 OF | | | NOA #02-0212.07. | | | | | | 3- ROOF TILE; | | | A) PROVIDE CORRECT NOA THAT CORRESPONDS TO FLORIDA | | | PRODUCT APPROVAL 3506. NEED NOA #02-0916.11. GO TO | | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING NOA. | | | | | | B) SPECIFY HOW IS ROOF TILE GOING TO BE FASTENED. IF | | | NAILS OR SCREWS, THEN SPECIFY NUMBER. IF USING | | | POLYFOAM, THEN PROVIDE CORRESPONDING PRODUCT APPROVAL | | | AS REQUIRED BY DCA RULE 9B-72. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|