| | NONCOMPLIANT |
| | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. FBC AS |
| | AMENDED. THIS ARTICLE ALSO IS AN EXTRACTION FROM THE |
| | EXEMPTION IN CHAPTER 471 OF THE FLORIDA STATUTES , |
| | 471.003, ALLOWING THE CONTRACTOR TO DRAW THEIR OWN |
| | PLANS. THE EXEMPTION INDICATES THE CONTRACTOR THAT IS |
| | INSTALLING THE WORK IS THE ONE COVERED UNDER THE |
| | EXEMPTION, 471.003(H).IN THE CASE OF THE ELECTRICAL |
| | PLANS , PLEASE HAVE THAT CONTRACTOR SUBMIT PLANS. |
| | |
| | 2} IT IS UNCLEAR IF THE SERVICE IS BEING REPLACED, |
| | UPGRADED OR EXISTING. IF NEW, PLEASE SUBMI TA RISER |
| | DIAGRAM PER 215.5 AND PROVIDE AIC RATINGS FOR SAME PER |
| | 110.9 & 10. |
| | |
| | 3} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 |
| | RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 4} THE ELECTRICALPANEL LOCATED IN THE KITCHEN MUST |
| | COMPLY WITH THE CLEARANCE REQUUIREMENTS OF 110.26, THAT |
| | INCLUDES THE PROXIMETY TO THE COUNTER. |
| | |
| | 5} PER 210.8(A)(6) ALL COUNTERTOP RECEPTACLES IN THE |
| | KITCHEN MUST BE GFCI PROTECTED. |
| | |
| | 6} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| | 106.3.5.4(8) FBC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |