| 2007-02-23 13:47:02 | DENIED BY BUILDING |
| | |
| | 1) PLANS ARE REQUIRED TO HAVE THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THEM. FBC* 106. |
| | |
| | 2) FBC * 106.1.1 REQUIRES CONSTRUCTION DOCUMENTS SHALL |
| | BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| | NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| | DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| | CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 3) FBC * 106.1.3 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | |
| | 4) FBC R312 AND FBC CHAPTER 11 REQUIRES AT LEAST ONE |
| | BATHROOM, LOCATED WITH MAXIMUM POSSIBLE PRIVACY, WHERE |
| | BATHROOMS ARE PROVIDED ON HABITABLE GRADE LEVELS, WITH |
| | A DOOR THAT HAS A 29-INCH (737 MM) CLEAR OPENING. |
| | HOWEVER, IF ONLY A TOILET ROOM IS PROVIDED AT GRADE |
| | LEVEL, SUCH TOILET ROOMS SHALL HAVE A CLEAR OPENING OF |
| | NOT LESS THAN 29 INCHES (737 MM). NEW MASTER BATH IS |
| | REQUIRED TO COMPLY. |
| | |
| | 5) PLANS NEED TO SPECIFY THE WINDOW TYPE (I.E. SINGLE |
| | HUNG, FIXED, ETC.), LOCATION OF EACH, ETC. AND WHICH |
| | ONES ARE BEING REPLACED. |
| | |
| | 6) SPECIFY WHICH EXTERIOR DOORS ARE BEING REPLACED. |
| | |
| | 7) PLANS NEED TO SPECIFY THE LOCATIONS WHERE THE |
| | DRYWALL IS BEING REPLACED. IF ALL THE WALLS AND CEILING |
| | DRYWALL IS BEING REPLACED SPECIFY THAT ON THE PLANS. |
| | |
| | 8) PLANS NEED TO SPECIFY WHICH WALLS ARE NEW AND WHICH |
| | ARE EXISTING. |
| | |
| | 9) PLANS NEED TO SPECIFY THE R-VALUE OF THE INSULATION |
| | AND THE LOCATIONS OF WHERE EACH TYPE IS BEING |
| | INSTALLED. |
| | |
| | 10) ENERGY CALC. FORM SPECIFIES EXTERIOR MASONRY WALLS |
| | WITH R-11 INSULATION. TYPICALLY MASONRY WALLS ARE |
| | INSULATED WITH R-5. SPECIFY HOW THE EXTERIOR MASORY |
| | WALLS ARE BEING INSULATED TO ACHIEVE R-11. |
| | |
| | 11) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS. SPECIFY THE FASTENER TYPE AND SPACING, |
| | THE CONNECTION TYPE, THE EDGE DISTANCE, WIND PRESSURE, |
| | SEPARATION DISTANCE, SPANS, ETC. CIRCLE THE APPROPRIATE |
| | ITEMS ON THE NOA AND FILL OUT ATTACHED INSTALLATION |
| | SCHEDULE OR PROVIDE ONE OF YOUR OWN |
| | |
| | 12) SUBMIT PRODUCT APPROVALS FOR THE STRUCTURAL WINDOW |
| | MULLIONS. |
| | |
| | |
| | 13) ON THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOF |
| | SYSTEM INDICATE WHICH ONE OF THE APPROVED SYSTEMS WILL |
| | BE INSTALLED. SEE PAGES 9-31 OF NOA. INDICATE THE |
| | FASTENING OPTION AND DESIGN PRESSURE THAT WILL BE USED |
| | TO INSTALL THE SYSTEM. IF ENHANCED FASTENING IS |
| | REQUIRED TO INCREASE THE DESIGN PRESSURES AT THE |
| | PERIMETER AND CORNER AREAS, SUBMIT RAS 117 CALCULATIONS |
| | AS REQUIRED BY LIMITATION #7. SEE PAGE 32. |
| | |
| | 14) THE FL COVER SHEET SUBMITTED FOR THE GAF MODIFIED |
| | ROOF SYSTEM IS NOT THE CORRECT ONE. THE CORRECT ONE IS |
| | FL 617-R1. |
| | |