| Plan Review Notes For Permit 07010753 |
| Permit Number |
07010753 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-11 13:58:26 | BUILDING REVIEW CHECKLIST: | | | 1- RAS 117 CALCULATIONS FOR FLAT ROOF SYSTEM: | | | A) ENGINEER'S CALCULATIONS REFER TO NOA 03-0501.02 | | | ASSEMBLY ON PAGE 28. NOA 03-0501.02 SUBMITTED SHOWS | | | PAGE 26 AS THE SELECTED ASSEMBLY. ASSEMBLY ON PAGE 28 | | | IS DIFFERENT THAN ASSEMBLY ON PAGE 26. PROVIDE MATCHING | | | INFORMATION. | | | | | | B)FROM NOA 03-0501.02 ENGINEER TO CLEARLY IDENTIFY | | | BASE SHEET FASTENING OPTION AND CORRECT DESIGN | | | PRESSURES. SPECIFY FASTENING TYPE AND CORRECT DESIGN | | | PRESSURES THAT MATCHSELECTED FASTENING OPTION. ONE | | | SUBMITTED DOESN'T MATCH. | | | | | | C)ENGINEER TO CLARIFY HOW CAN A 4" OVERLAP HAVE | | | TWO ROWS OF NAILS IF THE MINIMUM FASTENER SEPARATION | | | SHALL NOT BE LEES THAN 4"O.C.. SEE SEC. 8.1 OF RAS 117. | | | ALSO, PROVIDE MANUFACTURER'S APPROVAL OF PROPOSED | | | INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | D) ENGINEER IS USING THE CALCULATIONS FOR INSULATION | | | ATTACHMENT. THIS IS A NON-INSULATED SYSTEM. NEED TO USE | | | CORRECT EQUATIONS. SEE SEC. 10 OF RAS 117. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|