Date Text
2007-01-23 14:20:40DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A2 SANITARY RISER DIAGRAM: ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN AND IS NOT CODE COMPLIANT.
 PLEASE REFERENCE THE CODE COMPLIANT ISOMETRIC IN RED
 INK THAT REFLECTS THE FLOOR PLAN ATTACHED TO THE
 PLUMBING COMMENTS FOR THE RESUBMITTAL. PLEASE CORRECT
 AND RESUBMIT.
  
 2. SHEET A2 SANITARY RISER DIAGRAM: PER FBC-2004
 PLUMBING SECTION 1002.3 "S" TRAPS ARE PROHIBITED.
 PLEASE CORRECT AND RESUBMIT.
  
 3. SHEET A2 SANITARY RISER DIAGRAM: PER FBC-2004
 PLUMBING SECTION 1002.1 FIXTURES SHALL NOT BE DOUBLE
 TRAPPED. WATER CLOSETS HAVE AN INTEGRAL TRAP AND ONE
 (TRAP) NEED NOT BE INDICATED FOR THE WATER CLOSET ON
 THE DRAWINGS. PLEASE CORRECT AND RESUBMIT.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  