2007-01-23 08:19:21 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1}BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).
  
 2} SHOW THE PHYSICAL LOCATION OF ALL SERVICE EQUIPMENT
 ON THE PLAN SO THAT COMPLIANCE WITH 230.70(A)(1) MAY BE
 REVIEWED.
  
 3} INDICATE IF THEW SERVICE ON THE PLAN IS EXISTING OR
 PROPOSED, IF NEW PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.