| Plan Review Notes For Permit 07010693 |
| Permit Number |
07010693 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-12 16:00:53 | BUILDING REVIEW CHECKLIST: | | | 1- NOA #01-0424.03 SUBMITTED EXPIRED ON 03/08/2006. | | | NEED TO PROVIDE CURRENT PRODUCT APPROVAL. | | | | | | 2- SELECTED SYSTEM ON PAGE 26 IS LIMITED BY GENERAL | | | LIMITATION #9. IT CAN BE USED IN THIS AREA BECAUSE THE | | | DESIGN PRESSURES OF -45PSF ARE TOO LOW FOR THE REQUIRED | | | DESIGN PRESSURES AT PERIMETER AND CORNER AREAS. SEE | | | TABLE 1609.2.1(2) OF FBC 2004. SELECT ANOTHER APPROVED | | | ASSEMBLY. | | | | | | 3- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #7, THEN, PROVIDE ALL CALCULATIONS AS | | | REQUIRED BY THIS LIMITATION.IF NOA REQUIRES | | | CALCULATIONS TO BE DONE BY ARCHITECT, ENGINEER OR | | | REGISTERED ROOF CONSULTANT, THEN PROVIDE SUCH SIGNED | | | AND SEALED CALCULATIONS.SEE GENERAL LIMITATIONS ON | | | PAGE 35 OF NOA 01-0424.03. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|