| 2007-02-21 18:07:38 | BUILDING REVIEW FOURTH CHECKLIST: |
| | 1- GENERAL LIMITATION #7 ON FLAT ROOF SYSTEM NOA |
| | 06-0410.06 SUBMITTED REQUIRESRAS 117 NAIL ENHANCING |
| | CALCULATIONS FOR PERIMETER AND CORNER AREAS TO BE DONE |
| | AND SIGNED,SEALED BY AN ARCHITECT, ENGINEER OR |
| | REGISTERED ROOF CONSULTANT. PROVIDE SUCH CALCULATIONS |
| | AS REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA SUBMITTED. |
| | |
| | 2-A)IF SUBMITTING CALCULATIONS DONE BY ROBERT |
| | NIEMINEN, PE, THEN THEY NEED TO HAVE ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES |
| | AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | B) PROPOSED SPACING FOR NAIL ENHANCING AT PERIMETER |
| | AREA(PAGE 2 OF 2) DOESN'T MEET REQUIRED SPACING. |
| | PROVIDE ACTUAL RAS 117 CALCULATIONS TO SHOW SPACING. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) IF USING SUBMITTED ENGINEER'S REPORT, THEN COMPLY |
| | WITH LIMITATIONS OF USE #D AND CONCLUSIONS.NEED |
| | WITHDRAWAL TESTING FOR BASE SHEET FASTENERS AND |
| | QUALIFIED PROFESSIONAL TO DETERMINE BUILDING EXPOSURE |
| | CATEGORY AND ENCLOSURE CONDITIONS (SEE PAGE 3 OF 3). |
| | |
| | 3- INFORMATION SHOWN ON HIGH VELOCITY HURRICANE ZONE |
| | PERMIT APPLICATION DOESN'T MATCH ENGINEER REPORT |
| | SUBMITTED.SEE DESIGN PRESSURES AND LAPWIDTH.ON |
| | THE OTHER HAND, THIS FORMIS NOT REQUIRED IN THIS |
| | MUNICIPALITY. |
| | |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |