| 2007-01-11 16:47:21 | BUILDING REVIEW CHECKLIST: |
| | 1- SEE ATTACHED COPY OF CITY POLICY FOR ROOFING |
| | PERMITS. NEED THE FOLLOWING: |
| | A) FLAT ROOF SYSTEM NEED TO PROVIDE TECHNICAL REPORT |
| | THAT WAS SUBMITTED FOR FLORIDA PRODUCT APPROVAL FL1213. |
| | VISIT WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL RELEVANT |
| | INFORMATION.ONLY THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGES WERE SUBMITTED. SEE ATTACHED COPY OF CITY |
| | POLICY. |
| | |
| | B) PROVIDE FLORIDA PRODUCT APPROVAL FL1213 FOR 2004 |
| | CODE VERSION. ONE SUBMITTED IS FOR 2001. |
| | |
| | C) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING |
| | TO BE INSTALLED AS REQUIRED BY CITY POLICY. |
| | |
| | D) ON SELECTED ASSEMBLY CLEARLY IDENTIFY WHICH BASE |
| | SHEET FASTENING OPTION IS GOING TO BE INSTALLED. SEE |
| | CITYPOLICY. |
| | |
| | E) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT CORNER AND PERIMETER AREAS. SEE |
| | GENERAL LIMITATION #7 ON LAST PAGE OF NOA. CALCULATIONS |
| | NEED TO BE SIGNED AND SEALED BY ARCHITECT, ENGINEER OR |
| | REGISTERED ROOFING CONSULTANT. |
| | |
| | F) IF SELECTED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA |
| | BECAUSE OF THE REQUIRED DESIGN PRESSURES. |
| | |
| | 2- ROOF SHINGLES. PROVIDE COMPLETE TECHNICAL REPORT. |
| | ONLY THE FLORIDA PRODUCT APPROVAL FL3663 COVER PAGES |
| | WERE SUBMITTED. |
| | |