2007-02-08 09:06:29 
 ****************PROVISO****************
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 (C) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (D) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.