| Date |
Text |
| 2007-03-13 12:21:17 | *****UNSAT***** |
| | |
| | COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE BEEN |
| | SATISFIED WITH THE EXCEPTION OF THE FOLLOWING WHICH |
| | STILL NEED TO BE ADDRESSED: |
| | |
| | |
| | 01.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, |
| | SHALL BE REFERENCED.ON SHEET A-001 UNDER CODE |
| | CLASSIFICATION,ADD "NFPA 101 2003 EDITION" |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ON |
| | SHEET A-001 UNDER CODE CLASSIFICATION, ADD "NFPA 241" |
| | |
| | 08.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR |
| | WALL AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS, |
| | AND IN ALL OTHER AREAS.AS PER NFPA 101: 38.3.3.1 - |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | CLASS A OR B IN EXITS AND EXIT ACCESS CORRIDORS AND |
| | SHALL BE CLASS A, B, OR C IN ALL OTHER AREAS.PLEASE |
| | SPECIFY |
| | |
| | 09.INDICATE THE LOCATION OF THE 2A:10BC FIRE |
| | EXTINGUISHER WHICH SATIFIES THE 75' TRAVEL DISTANCE |
| | REQUIREMENT.PLEASE BE ADVISED THAT AT THE TIME OF |
| | FIRE INSPECTION FOR BUSINESS TAX SIGNOFF BY WEST PALM |
| | BEACH FIRE PREVENTION BUREAU, A FIRE EXTINGUISHER WILL |
| | BE LOCATED IN THE TENANT SPACE. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE (ON THE |
| | PLAN) EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |