| 2007-03-04 18:33:40 | *** UNSAT*** |
| | |
| | |
| | 1)NOTE:PLEASE KNOW TO QUALIFY UNDER "MANAGEMENT" |
| | MUST HAVE "QUALIFIED PERSONNEL" AS DEFINED ON THE NEC |
| | ART 100. |
| | |
| | 2) NOTE: PLEASE BE SURE TO STATE ALL MAXIMUM TIME FOR |
| | OC TYPE DEVICES TO BE 30 MINS PER 13-415.1.ABC.1.1, NOT |
| | STATED ON PLANS. |
| | |
| | 3) PLEASE SEE NO ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS, LIGHTING POWER DENSITIES SHOWN OR |
| | SUBMITTED. |
| | 13-415.1.AB.1.1, 13-415.2 |
| | |
| | ** PLEASE SEE THE PLANS WILL BE COMING BACK FOR OTHER |
| | TRADES AS THE ARCHITECT DID NOT DATE PLANS AS REQUIRED |
| | PER FS481.221 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |