| Date |
Text |
| 2007-01-15 08:22:52 | PLANS REMOVED FROM INCOMING FOR REVIEW, ROUTED BACK TO |
| | INCOMING AWAITING SPACE ON THE BOB BOARD. |
| 2007-01-15 08:22:42 | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. THIS IS |
| | REQUIRED ON ARCH COVER SHEET AS WELL AS ON ELECTRICAL. |
| | THE ELECTRICAL SHEET DOES CONTAIN SOME OF THESE |
| | ALREADY, HOWEVER PLEASE SEE MISSING. |
| | |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). (THE 2005 NEC IS SHOWN) |
| | 2002 NFPA-72 |
| | 2003 NFPA-101. |
| | |
| | 2) NOTE: PLEASE SEE THE WATER HEATER SYMBOL WHICH |
| | INDICATES A 60AMP MOLDED CASE SWITCH WHICH IS OK AS |
| | 30AMP OCP IS SHOWN IN PANEL. PLEASE SUBMIT THE |
| | MANUFACTURE?S SPECS/CUT SHEETS IF THIS IS A |
| | INSTA-HOT/TANK-LESS WATER HEATER UNIT. IF A STORAGE |
| | TYPE AS SHOWN ON PLUMBING PLANS THEN THE SPECS ARE NOTE |
| | REQUIRED FOR ELECTRICAL REVIEW. PLEASE SEE 422.17 FOR |
| | MINIMUM CLEARANCES AS THIS UNIT IS SHOWN AS 30 GALS AND |
| | DOES NOT SEEM THAT IS MAY FIT UNDER A SINK AS SHOWN. |
| | PLEASE BE SURE THE LISTING FROM A NATIONALLY RECOGNIZED |
| | TESTING LABORATORY IS SHOWN. (NRTL). 110.3, 90.7 |
| | |
| | 3) NOTE: PLEASE BE SURE TO INDICATE ALL CIRCUITS ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | PLEASE LABEL ALL LOCATIONS ON PANELS WHICH CORRELATE TO |
| | ROOMS/AREAS WHICH ARE BEING FED. THIS SHOULD BE MORE |
| | SPECIFIC. IE; OFFICE 1 RECEPTS,INTAKE RECEPTS, |
| | CONFERENCE RM ETC. |
| | THIS CAN BE DONE AT THIS TIME OR IT WILL BE REQUIRED |
| | BEFORE INSPECTION FOR FINAL. |
| | 106.1.2, 106.3.5.1.2 |
| | NEC 408.4, 310.16, 240.4 FOR VERIFICATION. |
| | |
| | 4) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORN, |
| | STROBES AND/OR HORN STROBE DEVICES PER FBC 11-4.28.1, |
| | .2 AND .3(4). |
| | PLEASE SEE LOBBY AREA WHICH DOES NOT SEEM TO INDICATE A |
| | DEVICE. 11-4.28.2 PLEASE SEE ANY OTHER LOCATIONS WHICH |
| | MAY BE BROUGHT UP BY FIRE MARSHAL' REVIEW. |
| | THE INSTALLATION OF ANY ADDITIONAL DEVICES TO THE |
| | EXISTING FIRE ALARM SYSTEM WILL BE REQUIRED UNDER |
| | SEPARATE PLANS, PERMIT, HOWEVER THESE REQUIRED LEVELS |
| | ARE TO BE SHOWN ON BASE PLANS. |
| | |
| | 5) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER |
| | 13-415.1.AB.1, PERFORMANCE CALCULATIONS PER 13-415.2. |
| | THESE ARE REQUIRED TO BE SIGNED DATED AND SEALED BY THE |
| | DESIGNER OF RECORD. |
| | PLEASE SUBMIT A FIXTURE LEGEND FOR LIGHTING FIXTURES |
| | TO BE INSTALLED AND CORRELATE WITH THE IDENTIFICATION |
| | ON PLANS. PLEASE BE SURE TO CORRELATE WITH THE |
| | PERFORMANCE CALCULATIONS AND ENERGY CALCULATIONS. |
| | PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER |
| | 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SUBMIT AUTOMATED LIGHTING CONTROL METHODS, |
| | SCHEDULING, DEVICES AND TYPES OF DEVICES. |
| | PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE |
| | DEVICES. (30 MINS FOR OCCUPANCY TYPE AND 4HRS MAX FOR |
| | TIMER TYPE. THE TIMES ARE NOTED, HOWEVER ANY NEW |
| | DEVICES IF TYPICAL THEN WOULD CONTAIN THE SAME |
| | IDENTIFICATION. |
| | PLEASE KNOW THAT MOST ARE SHOWN; HOWEVER PLEASE SEE |
| | MISSING AT ENTRANCE INTO SPACE. |
| | PLEASE PROVIDE A DETAIL FOR THE CIRCUITING THE |
| | EMERGENCY AND EXIT LIGHTS. (THERE IS A NOTE ON PLANS, |
| | HOWEVER SUBMIT DETAIL AS NUMEROUS SITUATIONS IN THE |
| | JURISDICTION HAS HAD THESE FIXTURES BEING WIRED ON THE |
| | LOAD SIDE OF THESE DEVICES. |
| | PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR REVIEW, |
| | A COMPLETE REVIEW FOR COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | |
| | 6) NOTE: PLEASE CLARIFY THE LOCATIONS O THE PANELS AS |
| | NOTED. PLEASE ALSO CLARIFY WHERE PANEL COVER MENTIONS |
| | THE COVERS ARE NOT LOCKABLE? |
| | PLEASE PROVIDE INFORMATION ON PLANS WHETHER BUILDING IS |
| | UNDER MANAGEMENT OF QUALIFIED PERSONNEL. |
| | 240.24, (A), (B), (C). |
| | |
| | |
| | 7) NOTE: PLEASE CLARIFY IN SERVICE CALCULATIONS ARE |
| | SHOWN AT 125% FOR CONTINUOUS LOADS. |
| | 215.3, 230.42 ETC. |
| | 220.12, 220.14, 220.43, 220.44 ETC. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |