| Plan Review Notes For Permit 07010580 |
| Permit Number |
07010580 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-05-21 13:20:28 | NOTE: GAS PERMIT REQUIRED | | | | | | ****************PROVISO**************** | | | THE CORRECT TABLE FOR UNDERGROUND POLYETHLENE (PE) | | | NATURAL GAS PIPE FOR A 0.5 PSI IS 402.4(20) | | | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | | INGS REQUIRED PER SECTION 304.5 OR | | | SECTION 304.6 SHALL BE INSTALLED. | | | MINIMUM 2,500 CUBIC FEET REQUIRED. | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|