| 2007-04-03 11:48:32 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **OK** |
| | |
| | 2. **OK** |
| | |
| | 3. **OK** |
| | |
| | NOW THAT THE ABOVE GROUND GAS PIPING HAS BEEN |
| | ESTABLISHED AS BEING GALVANIZED STEEL ON THE |
| | RESUBMITTAL THE FOLLOWING ARE NEW COMMENTS: |
| | |
| | 4. SHEET P-3 ISOMETRIC GAS RISER DIAGRAM: GAS PIPE TO |
| | 19O,000 BTU TANKLESS W/HTR. NEEDS TO BE INCREASED TO |
| | ONE INCH (1") PER FBC-2004 FUEL GAS TABLE 402.4 (2). |
| | PLEASE REFERENCE THE ATTACHED GAS SIZING TABLES TO THE |
| | GAS COMMENTS INDICATING THE NEED FOR THE PIPING |
| | INCREASE. |
| | |
| | 5. SHEET P-3 ISOMETRIC GAS RISER DIAGRAM GAS PIPING TO |
| | THE NEW RANGE IS CONFUSING, ISOMETRIC IS INDICATING |
| | THREE SEPERATE CONNECTIONS TO THE APPLIANCE WITH A BTU |
| | LOAD OF 44,000 BTU'S. SHEET A-1 IS INDICATING A NEW GAS |
| | RANGE WITHPOSSIBLY SIX BURNERS (FOUR INDIVIDUAL |
| | BURNERS AND POSSIBLY TWO SIDE BURNERS FOR A SIDE |
| | GRIDDLE OR GRILL, INDIVIDUAL BURNER BTU LOAD IS AT |
| | 15,000 WITH A TOTAL BTU LOAD INCLUDING THE OVENS IS |
| | POSSIBLY 137,000 BTU,S)PLEASE SUBMIT MANUFACTURER |
| | SPECIFICATIONS OF ALL APPLIANCES (GRILL, TANKLESS WATER |
| | HEATER, AND NEW GAS RANGE) VERIFYING THE BTU LOADS WITH |
| | THE ISOMETRIC AND SHOWING LISTINGS FROM A NATIONALLY |
| | RECOGNIZED TESTING LABORATORY (NRTL). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |