2007-01-22 08:58:03DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1,
 CITY OF WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-3 SANITARY ISOMETRIC: A} PER FBC-2004
 CHAPTER 1, SECTION 106.3.5.4, PLEASE SIZE ALL FIXTURE
 TRAPS. B} PER FBC-2004 PLUMBING SECTION406.3 WASTE
 CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. C} PER FBC-2004 PLUMBING SECTION 708.9 ACCESS
 SHALL BE PROVIDED TO ALL CLEANOUTS. PLEASE INDICATE THE
 CLEANOUT FOR THE WASHING MACHINE AT FOUR FEET ABOVE
 FINNISH FLOOR (4' A.F.F.) ON THE RESUBMITTAL.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  