Plan Review Notes
Plan Review Notes For Permit 07010580
Permit Number 07010580
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-21 19:06:09DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE WORK DESCRIPTION ON THE APPLICATION IS FOR
 INTERIOR REMDELING. THE PLANS SHOW NEW EXTERIOR WALLS
 AND INCREASING OPENING SIZE, IN ADDITION TO REPLACING
 WINDOWS AND DOORS. PLEASE REVISE WORK DESCRIPTION ON
 THE APPLICATION.
  
 3) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS. SEE
 2004 FBC EXISTING BUILDING CHAPTER 3.
  
 4)PROVIDE AT LEAST ONE BATHROOM, LOCATED WITH MAXIMUM
 POSSIBLE PRIVACY, WHERE BATHROOMS ARE PROVIDED ON
 HABITABLE GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH
 (737 MM) CLEAR OPENING AS REQUIRED BY R322.1.1 AND FBC
 CHAPTER 11.
  
 5) THE PLANS SPECIFY MARVIN WINDOWS AND DOORS ON A4 AND
 A5 AND DO NOT SPECIFY OR EQUAL. THE PRODUCT APPROVALS
 SUBMITTED ARE FOR PGT WINDOWS AND DOORS. PLEASE REVISE
 PLANS.
  
 6) THE MASTER BEDROOM WINDOW IS LABELED"C" ON SHEET
 A1 AND THE WINDOW SCHEDULE ON A4 HAS "D" FOR THIS
 WINDOW. PLEASE CORRECT.
  
 7) THE NEW MASTER BEDROOM WINDOW IS REQUIRED TO COMPLY
 WITH R310.1 FOR EMERGENCY ESCAPE AND RESCUE OPENINGS.
 SHOW COMPLIANCE.
  
 8) ON A3 THE REAR (WEST) ELEVATION IS INCORRECTLY
 LABELED. PLEASE CORRECT.
  
 9) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS.
 SPECIFY THE FASTENERS AND SPACING.
  
 10) PROVIDE A STRUCTURAL DETAIL AT THE ENLARGED OPENING
 FOR THE NEW FRENCH DOOR. SPECIFY WALL AND BEAM
 REINFORCEMENT.
  
 11) PROVIDE STRUCTURAL DETAILS FOR THE NEW CBS IN-FILL
 WALLS AT THE MASTER BEDROOM ALCOVE AND AT THE FAMILY
 ROOM. SPECIFY REINFORCEMENT, TIE TO EXISTING STRUCTURE,
 LINTELS, BEAMS, ETC.
  
 12) PROVIDE STRUCTURAL DETAILS FOR THE CONSTRUCTION OF
 THE ARCH ABOVE THE NEW ARCH TOP WINDOW AT MASTER
 BEDROOM ALCOVE.
  
 13) SUBMIT 2 CURRENT PRODUCT APPROVALS FOR STRUCTURAL
 MULLIONS.
  
 14)PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG
 WINDOWS AND HORIZONTAL SLIDING WINDOWS WHICH ARE NOT
 THE TYPES OF WINDOWS SPECIFIED ON THE PLANS AS BEING
 REPLACED. THE PLANS APPEAR TO SPECIFY THE NEW WINDOWS
 AS CASEMENT AND FIXED WINDOWS. PLEASE CLARIFY WINDOW
 TYPES, SIZES AND LOCATIONS..
  
 15) THE PRDOUCT APPROVALS FOR THE PGT HORIZONTAL SLIDER
 HAS BEEN REVISED. SUBMIT NOA 03-0612.06 WITH STATE
 COVERSHEET.
  
 16) THE COVERSHEET FOR THE PGT FIXED WINDOWS IS FOR THE
 2001 CODE AND HAS BEEN REVISED. REPLACE PAGE 6 OF THE
 NOA WHICH IS ILLEGIBLE.
  
 17) THE COVERSHEET FOR THE PGT CASEMENTWINDOWS IS FOR
 THE 2001 CODE AND HAS BEEN REVISED. THE NOA HAS BEEN
 REVISED TO 05-1129.11. SUBMIT CURRENT COPIES OF BOTH.
  
 18) THE NOA FOR THE PGT FRENCH DOORS IS EXPIRED. SUBMIT
 CURRENT NOA. SEE WWW,FLORIDABUILDING .ORG.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  