| Plan Review Notes For Permit 07010563 |
| Permit Number |
07010563 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-23 10:39:56 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SHEET D-1 SANITARY RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN SHEET 1. PLEASE REFERENCE AN ATTACHED | | | SANITARY RISER DIAGRAM TO THE PLUMBING COMMENTS | | | REFLECTING THE FLOOR PLAN FOR THE RESUBMITTAL. | | | | | | 2. SHEET D-1 SANITARY RISER DIAGRAM: PLEASE DELETE | | | @1-1/2" BY THE LAV. VENT ON THE RESUBMITTAL. | | | | | | 3. SHEET D-1 SANITARY RISER DIAGRAM INDICATES 4" TO | | | SEPTIC SEWER, DOES RESIDENCE HAVE A SEPTIC TANK IF NOT | | | PLEASE DELETE SEPTIC SEWER AND ADD SANITARY SEWER IN | | | ITS PLACE ON HTE RESUBMITTAL. | | | | | | **********IMPORTANT INFORMATION | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|