| 2007-02-28 16:10:15 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC |
| | CHAPTER 13. |
| | |
| | 4) THERE IS A TYPO ON SHEET 1 FOR THE INTERNAL PRESSURE |
| | COEFFIECENT. IT SHOULD READ + / - 0.18. |
| | |
| | 5)R807.1 ATTIC ACCESS . |
| | IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF |
| | CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED |
| | TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 ) |
| | AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR |
| | GREATER. |
| | THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22 |
| | INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE |
| | LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE |
| | LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED |
| | HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME |
| | POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3 |
| | FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS |
| | LOCATED IN ATTICS. SPECIFY HOW ATTIC ACCESS TO |
| | ADDITIONS WILL BE ACHIEVED. |
| | |
| | 6) A PRODUCT APPROVAL WAS SUBMITTED FOR A MASONITE |
| | INTERNATIONAL EXTERIOR DOOR. THE PLANS AND WORK |
| | DESCRIPTION ON THE PERMIT DO NOT SPECIFY ANY NEW |
| | EXTERIOR DOORS. ALSO THE PRODUCT APPROVAL THAT WAS |
| | SUBMITTED IS EXPIRED. |
| | |
| | 7) SPECIFY THE MOUNT TYPE, FASTENER TYPE & SPACING AND |
| | REQUIRED WINDLOAD DESIGN PRESSURE FOR THE HURRICANE |
| | PANELS. CIRCLE THE APPROPRIATE ITEMS ON THE PRODUCT |
| | APPROVALS. |
| | |
| | 8) THE VALUE OF THE WORK HAS BEEN INCREASED BASED ON |
| | ICC CONSTRUCTION COSTS. ADDITIONAL PERMIT FEES ARE |
| | DUE. |
| | |