| Plan Review Notes For Permit 07010479 |
| Permit Number |
07010479 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-01-22 13:12:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 3RD REVIEW; FROM PREVIOUS LIST: | | | | | | 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES | | | (CORNER AND PERIMETER, ZONES 2 AND 3).SUBMIT | | | CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER GENERAL | | | LIMITATION #7 ON THE MIAMIDADE NOA. | | | | | | THIS IS BEING REQUESTED BECAUSE THE FASTENERS YOU HAVE | | | SPECIFIED ON THE HIGH VELOCITY HURRICANE ZONE UNIFORM | | | PERMIT APPLICATION FORM, 4 IN THE FIELD, 7 PERIMETER, | | | 10 CORNER DOES NOT APPEAR TO BE COMPLIANT.EXPLAIN HOW | | | YOU HAVE DETERMINED FOUR FASTENERS PER BOARD FOR THE | | | FIELD WHEN THE PRODUCT APPROVAL STATES ONE PER 2 SQUARE | | | FEET, AND THIS IS A 4X4 INSULATION BOARD.(4X4=16, | | | DIVIDED BY 2=8).PROVIDE CALCULATIONS. | | | |
|