2007-01-22 13:12:44****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 3RD REVIEW; FROM PREVIOUS LIST:
  
 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES
 (CORNER AND PERIMETER, ZONES 2 AND 3).SUBMIT
 CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER GENERAL
 LIMITATION #7 ON THE MIAMIDADE NOA.
  
 THIS IS BEING REQUESTED BECAUSE THE FASTENERS YOU HAVE
 SPECIFIED ON THE HIGH VELOCITY HURRICANE ZONE UNIFORM
 PERMIT APPLICATION FORM, 4 IN THE FIELD, 7 PERIMETER,
 10 CORNER DOES NOT APPEAR TO BE COMPLIANT.EXPLAIN HOW
 YOU HAVE DETERMINED FOUR FASTENERS PER BOARD FOR THE
 FIELD WHEN THE PRODUCT APPROVAL STATES ONE PER 2 SQUARE
 FEET, AND THIS IS A 4X4 INSULATION BOARD.(4X4=16,
 DIVIDED BY 2=8).PROVIDE CALCULATIONS.
  