| 2007-01-12 09:36:30 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 2ND REVIEW; FROM PREVIOUS LIST: |
| | |
| | 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES.A |
| | NOTE WAS PUT ON THE PLAN, "FASTENING FLAT AREA, FIELD |
| | 4", PERIMETER 6", CORNER 8", PERIMETER ALL AROUND 6'". |
| | IT IS NOT CLEAR WHAT THIS IS FOR.THE FIELD HAS A |
| | CLOSER FASTENING THAN CORNER AND PERIMETER BUT THE |
| | CORNER AND PERIMETER ZONES HAVE A HIGHER PRESSURE. ALSO |
| | FASTENING IS NOT CLEAR; YOU ARE USING INSULATION BOARD. |
| | SUBMIT CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER |
| | GENERAL LIMITATION #7 ON THE MIAMIDADE NOA. |
| | |
| | 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF |
| | RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED |
| | BY DOR.THE ARCHITECT STATES THAT THIS IS NOT AN |
| | APPROVED PRODUCT AND APPROVES IT ONLY IF IT IS AN |
| | EQUIVALENT.THE DOR IS TO MAKE THAT DETERMINATION; |
| | PLAN REVIEW IS TO REVIEW FOR MINIMUM CODE. |
| | |
| | 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT |
| | APPROVALS, REVIEWED BY DOR.THE PRODUCT APPROVAL |
| | SUBMITTED (HANSON) IS ACCEPTABLE, AS IS THE FASTENING |
| | INDICATED, BUT WAS NOT REVIEWED BY DOR. |