Plan Review Notes
Plan Review Notes For Permit 07010479
Permit Number 07010479
Review Stop B
Sequence Number 2
Notes
Date Text
2007-01-12 09:36:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 2ND REVIEW; FROM PREVIOUS LIST:
  
 1.)SPECIFY ENHANCED FASTENING FOR PERIMETER ZONES.A
 NOTE WAS PUT ON THE PLAN, "FASTENING FLAT AREA, FIELD
 4", PERIMETER 6", CORNER 8", PERIMETER ALL AROUND 6'".
 IT IS NOT CLEAR WHAT THIS IS FOR.THE FIELD HAS A
 CLOSER FASTENING THAN CORNER AND PERIMETER BUT THE
 CORNER AND PERIMETER ZONES HAVE A HIGHER PRESSURE. ALSO
 FASTENING IS NOT CLEAR; YOU ARE USING INSULATION BOARD.
 SUBMIT CALCULATIONS IN ACCORDANCE WITH RAS117 AS PER
 GENERAL LIMITATION #7 ON THE MIAMIDADE NOA.
  
 2.)PRODUCT APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.ENHANCED FASTENING TO BE REVIEWED
 BY DOR.THE ARCHITECT STATES THAT THIS IS NOT AN
 APPROVED PRODUCT AND APPROVES IT ONLY IF IT IS AN
 EQUIVALENT.THE DOR IS TO MAKE THAT DETERMINATION;
 PLAN REVIEW IS TO REVIEW FOR MINIMUM CODE.
  
 3.)THE PLAN SHOWS A TILE ROOF.PROVIDE PRODUCT
 APPROVALS, REVIEWED BY DOR.THE PRODUCT APPROVAL
 SUBMITTED (HANSON) IS ACCEPTABLE, AS IS THE FASTENING
 INDICATED, BUT WAS NOT REVIEWED BY DOR.