| Date |
Text |
| 2007-02-21 16:01:57 | *****DENIED***** |
| | |
| | |
| | 01.THE 2003 EDITION OF NFPA 101 AND THE FLORIDA FIRE |
| | PREVENTION CODE 2004 SHALL BE REFERENCED.SEE SHEET |
| | GV-101 |
| | |
| | 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 03.FIRE DEPARTMENT ACCESS ROADS SHALL BE MAINTAINED |
| | THROUGHOUT CONSTRUCTION. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUNTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.LANDSCAPING SHALL NOT OBSTRUCT OR INTERFERE WITH |
| | ACCESS TO THE FIRE HYDRANT, FIRE DEPARTMENT CONNECTION, |
| | OR ANY OTHER FIRE PROTECTION EQUIPMENT. |
| | |
| | 06.WHEN/IF IT IS NECESSARY TO SHUT DOWN FIRE |
| | PROTECTION SYSTEMS, THE FIRE DEPARTMENT SHALL BE |
| | NOTIFIED WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED |
| | TO SERVICE. |
| | |
| | 07.PROVIDE THE INTERIOR FINISH FOR THE NEW |
| | CONSTRUCTION.INTERIOR WALL AND CEILING FINISH |
| | MATERIAL SHALL BE CLASS A OR CLASS B FOR THE EXITS AND |
| | IN EXIT ACCESS CORRIDORS, AND SHALL BE CLASS A, CLASS |
| | B, OR CLASS C IN ALL OTHER AREAS. |
| | |
| | 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| | |
| | 09.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE |
| | NUMERICAL ADDRESS ON THE BUILDING TO BE VISIBLE FROM |
| | GREENWOOD AVENUE.AS PER WEST PALM BEACH CODE, THOSE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH.IF THE BUILDING IS SET-BACK FROM THE |
| | STREET OR ROADSIDE AND ARE NOT PLAINLY VISIBLE, A |
| | MONUMENT SIGN OR MARQUEE WITH THE ADDRESS WILL BE |
| | REQUIRED IN ADDITION TO THE BUILDING NUMBER. |
| | |
| | 10.IF THE BUILDING IS EQUIPPED WITH A KNOX-BOX |
| | (KEY-ENTRY BOX), WILL THE DEVICE NEED TO BE RELOCATED |
| | AS PER THE SCOPE OF THE NEW CONSTRUCTION?IF SO, |
| | INDICATE LOCATION ON THE PLANS. |
| | |
| | 11.THE EXISTING FIRE DEPARTMENT CONNECTION (FDC) |
| | SHALL NOT BE REMOVED AND CAPPED UNTIL SUCH TIME THAT |
| | THE NEW PIV AND FDC IS INSTALLED AND IN SERVICE. |
| | |
| | 12.KNOX LOCKING CAPS WILL BE REQUIRED FOR THE NEW |
| | FIRE DEPARTMENT CONNECTION (FDC).CONTACT WEST PALM |
| | BEACH FIRE PREVENTION (561-804-4724) FOR APPLICATIONS. |
| | |
| | 13.PROVIDE A LAYOUT OF THE EXISTINGFIRE ALARM SYTEM |
| | IN CONJUNCTION WITH THE NEW CONSTRUCTION. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS |
| | ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |