Text |
| 2007-01-30 08:01:56 | *** UNSAT **** |
| | |
| | *** IMPORTANT*** |
| | * PLEASE KNOW THAT BASED ON THE COMMENTS BELOW AND |
| | PLANS NOT BEING COMPLETE AT THIS TIME, WHEN PLANS ARE |
| | RESUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS MADE |
| | WHICH WERE NOT MADE ON THIS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE CODES REFLECTED ON PLANS ARE NOT |
| | CORRECT. |
| | PLEASE SEE THAT MANY OF THE CODES REFLECTED WENT OUT IN |
| | OCT 1ST OF 2005. PLEASE ALSO SEE THAT AS OF DECEMBER |
| | 8TH, 2006 THE CODES CHANGED TO THE 2006 REVISIONS TO |
| | THE 2004 FBC. PLEASE SEE THIS INCLUDES ALL MECHANICAL, |
| | PLUMBING BUILDING ETC. |
| | PLEASE SEE THAT AS OF THAT SAME DATE THE STATE ALSO |
| | ADOPTED THE NEW 2005 NFPA-70 (NEC). |
| | PLEASE SEE THE INCORRECT NFPA-101, 1 AND 72 ARE |
| | REFLECTED. |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM ON ARCHITECTURAL |
| | COVE SHEET AND ELECTRICAL PLANS AT A MINIMUM. |
| | 2005 NFPA-70, 2002 NFPA-72, 2003 NFPA-101, 2003 |
| | NFPA-1. |
| | |
| | ** PLEASE KNOW THAT OTHER CODES FROM OTHER TRADES MAY |
| | ALSO BE STATED TO BE DONE, THIS IS FOR ELECTRICAL |
| | REVIEW ONLY. |
| | |
| | 2) NOTE: PLEASE SEE THAT THE BASE ELECTRICAL PLANS |
| | SHALL INDICATE THE MINIMUM LEVELS FOR ALL HORNS, |
| | STROBES, OR HORN/STROBE DEVICES AS REQUIRED UNDER FBC |
| | 2004 11-4.28.1,.2 AND .3(4). THE PLANS NEED TO INDICATE |
| | THESE DEVICES ON THE SYMBOL LEGENDS AND CORRELATE WITH |
| | PLANS. |
| | PLEASE BE SURE ALL MINIMUM LEVELS AS REQUIRED ARE |
| | INDICATED. |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| | |
| | 3) NOTE: PLEASE KNOW THAT THE LIGHTNING PROTECTION |
| | SYSTEM SHALL BE REQUIRED TO BE UNDER A SEPARATE |
| | PERMIT. |
| | |
| | 4) NOTE: PLEASE PROVIDE MINIMUM WIND LOAD INFORMATION |
| | FOR ANY SITE LIGHTING POLES. PLEASE ALSO BE SURE THE |
| | INFORMATION PROVIDED SHALL INCLUDE THE EFFECTIVE |
| | PROJECTED AREA (EPA) OF THE FIXTURE. PLEASE KNOW THAT |
| | THE MINIMUM WIND LOAD FOR POLES SHALL BE STATED ON |
| | PLANS AND IF THE INFORMATION FOR THE POLE CALCULATIONS |
| | IS NOT KNOWN AT THIS TIME BASED ON WHETHER OR NOT THE |
| | MANUFACTURE HAS BEEN CHOSEN, THIS MAY BE SET UP AS A |
| | *PROVISO*, HOWEVER THE MINIMUM WIND SPEEDS SHALL BE ON |
| | PLANS. |
| | ** PLEASE SEE FBC 2004. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP FOR |
| | BRANCH/CIRCUITS AND FEEDERS PER 13-413.1ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SUBMIT MINIMUM ENERGY CALCULATIONS AND |
| | PERFORMANCE CALCULATIONS BASED ON THE AREA BEING DONE |
| | AS A SHELL. PLEASE SEE 13-415.1.AB.1 AND 13-415.2. * |
| | PLEASE KNOW THESE SHALL BE SIGNED, DATED AND SEALED, BY |
| | THE ENGINEER OF RECORD. 13-103.1.1.1 |
| | |
| | 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS ARE REQUIRED |
| | FOR AUTOMATED SHUTTING DOWN OF LIGHTING. PLEASE SEE FBC |
| | 2004 (2006 REVISIONS) 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 8) NOTE: PLEASE SEE MISSING DEDICATED EQUIPMENT ROOM |
| | FOR THE ELEVATOR. PLEASE SEE THE NEC 620. 620.22, |
| | 620.23, 620.24 AND 620.51. |
| | PLEASE SEE MISSING THE DEDICATED CIRCUITS FOR THIS ROOM |
| | AND OTHER ELEVATOR RELATED LIGHTING ETC WHICH MAY NOT |
| | FEED ANY OTHER AREAS. PLEASE SEE PLANS INDICATE THESE |
| | CIRCUITS FEEDING OTHER LIGHTING OUTSIDE OF THESE |
| | AREAS. |
| | PLEASE ALSO SEE THE STATE ELEVATOR CODE. |
| | PLEASE ALSO PROVIDE MORE INFORMATION FOR THE ELEVATOR |
| | MOTOR ITSELF. PLEASE VERIFY THE CONDUCTORS ETC. 620.11, |
| | 620.12 ETC. |
| | |
| | 9) NOTE:PLEASE VERIFY THE LOCATION OF THE ROOF TOP |
| | GFI REQUIRED FOR A/ C EQUIPMENT PER 210.63 AND |
| | 210.8(B)(3). |
| | |
| | 10) NOTE: PLEASE PLACE ALL FIXTURE DESIGNATIONS ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED FIXTURE LEGEND. |
| | PLEASE KNOW THAT MANY AREAS CAN NOT BE VERIFIED AT THIS |
| | TIME. |
| | FBC 106.1.2. |
| | |
| | 11) NOTE: PLEASE SEE MISSING EMERGENCY BATTERY BACK UP |
| | LIGHTS REQUIRED IN STAIRS, ELEVATOR EQUIPMENT ROOM, |
| | ELECTRICAL EQUIPMENT ROOM. |
| | NFPA-101 7.8, 7.9 |
| | NFPA-70 700.16, AND 700.12E. |
| | |
| | 12) NOTE: PLEASE SUBMIT AND PROVIDE PHOTO-METRICS FOR |
| | ALL EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3, |
| | 7.9.2.2. |
| | |
| | 13) NOTE: PLEASE SEE RISER AS SUBMITTED IS NOT COMPLETE |
| | AT THIS TIME AND THERE ARE SEVERAL ITEMS WHICH CAN NOT |
| | BE REVIEWED FOR CODE COMPLIANCE. |
| | PLEASE SUBMIT A COMPLETE ELECTRICAL RISER DIAGRAM WITH |
| | ALL SERVICE ENTRANCE CONDUCTORS, FEEDERS, GROUNDING, |
| | SIZES OF ALL EQUIPMENT, LOCATIONS OF ALL EQUIPMENT, AIC |
| | RATINGS FOR ALL SERVICE EQUIPMENT ETC. |
| | ** PLEASE SEE 110.9, 215.5, 240.4, 310.16, 230.70, |
| | 230.76, 230.79,250.50, 250.54, 250.56, 250.66, 240.24, |
| | 110.26 ETC. |
| | PLEASE SEE THAT THESE ARE ALL FROM THE 2005 NEC. |
| | |
| | 14) NOTE: PLEASE SEE NFPA-72 4.4.1 MORE SPECIFICALLY |
| | 4.4.1.4.1, 4.4.1.4.2.1 AND .2.2. |
| | PLEASE INDICATE HOW THIS PROTECTION WILL BE PROVIDED |
| | FOR THE DEDICATE BRANCH CIRCUIT FOR THE FIRE ALARM |
| | CONTROL PANEL. |
| | ** PLEASE KNOW THAT ANY LOCK-OFF DEVICES SHALL INCLUDE |
| | SUCH A DEVICE WHICH INCLUDES THE DEVICE AS AN INTEGRAL |
| | PART OF THE BREAKER. A *SNAP ON/CLIP ON* TYPE DEVICE IS |
| | NOT ACCEPTABLE TO THIS AHJ. |
| | 110.3, 90.4. |
| | |
| | 16) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | SERVICE AND EACH OF THE PANELS AS BEING SHOWN EVEN |
| | THOSE BEING SET ASIDE FOR FUTURE USE. PLEASE SEE THE |
| | ONLY PANEL SHOWN WHICH IS THE NHP DOES NOT INCLUDE A |
| | LOAD SUMMARY OR HOW THE SERVICE WAS SIZED. |
| | PLEASE SEE NOTE #13 ABOVE AS THE SERVICE SIZE OR |
| | CONDUCTORS ARE NOT COMPLETE THE SIZE OF THE SERVICE CAN |
| | NOT BE DETERMINED AT THIS TIME. |
| | PLEASE SEE ALL OF 220. |
| | PLEASE ALSO SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS |
| | LOADS AND LARGEST MOTORS LOADS AT 125%. |
| | FBC ADMIN SECTION 106.3.5.1.2, 106.1.2 |
| | |
| | 17) NOTE: PLEASE SEE NOTE ABOVE (#13) WHICH REQUEST THE |
| | AIC RATINGS FOR ALL EQUIPMENT. PLEASE BE SURE THESE |
| | CORRELATE WITH THE DIVISION SPEC SUBMITTED. 106.1.2. |
| | NEC 110.9 |
| | |
| | 18) NOTE: PLEASE CLARIFY PANEL NHP WHICH INDICATE MORE |
| | THAN 42 SPACES WHICH IS NOT PERMITTED PER 408.35. |
| | PLEASE PROVIDE MORE INFORMATION ON THIS PANEL AS THIS |
| | DOES NOT SHOW BEING A TWO SECTION OR CONTAINING |
| | FEED-THRU LUGS ETC. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-29 12:49:58 | IN ELEC FOR REVIEW (ONE ROLL) AND PERMIT APPLICATION. |