| 2007-07-06 17:27:44 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | WEST PALM BEACH CITY CODE |
| | |
| | ***FROM PREVIOUS REVIEW: |
| | |
| | ********FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" |
| | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED |
| | AND STAMPED BY DBPR PLAN REVIEW. |
| | ****NO RESPONSE, NOT ADDRESSED.--NOW THE REQUIRED |
| | SHEETS THAT WERE STAMPED BY DBPR HAVE BEEN REMOVED. |
| | EACH SET OF PLANS SHALL HAVE A DBPR STAMPED SHEET WITH |
| | THE TWO PAGE WORKSHEETS ATTACHED. |
| | ******RESPONSE NOTED FROM THE ENGINEER, BUT THIS HAS |
| | NOT BEEN ADDRESSED. I TALKED TO TONY BONO AND INDICATED |
| | THAT I WOULD TAKE CARE OF THIS "WORKSHEET" ISSUE, BUT |
| | SINCE THERE ARE OTHER COMMENT RESPONSES TO BE ADDRESSED |
| | FOR THE GAS RESPONSE, AND WITH THE WORKLOAD WE HAVE, |
| | RATHER THAN SLOW DOWN OUR PROCESS, I LEFT THIS |
| | REQUIREMENT TO THE CONTRACTOR TO ADDRESS. |
| | |
| | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, |
| | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE |
| | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. |
| | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. #3434. |
| | ****RESPONSE NOTED. SUBJECT NOT ADDRESS. I WILL TRY TO |
| | GET THE INFORMATION FROM THE ENVIRONMENTAL COMPLIANCE |
| | MANAGER. |
| | ******STILL WAITING FOR SOME RESPONSE ON THIS ISSUE. |
| | |
| | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, NOT ADDRESSED. |
| | ********RESPONSE NOTED, BUT 4 OUT OF 6 GAS APPLIANCES |
| | HAVE ONLY A COVER SHEET FROM THE SUPPLIER AND NOT THE |
| | MANUF. SHEETS AS REQUESTED. THE MANUF. SHEETS ARE |
| | REQUIRED FOR ITEMS MARK G2, G6, G7 & G8 SHOWING A |
| | LISTING, INDICATE MODEL NUMBER, AND SHOW THE BTU LOAD |
| | THAT CORRELATES WITH THE PLUMBING SERVICE SCHEDULE AND |
| | THE GAS RISER DIAGRAM. |
| | |
| | C. N/A |
| | D. N/A |
| | E. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |