| Plan Review Notes For Permit 07010448 |
| Permit Number |
07010448 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-07-06 17:09:33 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | ****FROM THE PREVIOUS REVIEW: | | | ********FROM PREVIOUS REVIEWS: | | | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARATE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, NOT ADDRESSED | | | ********RESPONSE NOTED, BUT 4 OUT OF 6 GAS APPLIANCES | | | HAVE ONLY A COVER SHEET FROM THE SUPPLIER AND NOT THE | | | MANUF. SHEETS AS REQUESTED. THE MANUF. SHEETS ARE | | | REQUIRED FOR ITEMS MARK G2, G6, G7 & G8 SHOWING A | | | LISTING, INDICATE MODEL NUMBER, AND SHOW THE BTU LOAD | | | THAT CORRELATES WITH THE PLUMBING SERVICE SCHEDULE AND | | | THE GAS RISER DIAGRAM. | | | | | | C. N/A | | | D. N/A | | | E. OK | | | | | | ****NEW COMMENT: | | | | | | 1B. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|