| 2007-06-20 10:29:41 | *** UNSAT 3RDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | NEED TO COORDINATE WITH THE PLANS FOR THE NUMBER OF |
| | FIXTURES, THE WATTAGE FOR FIXTURES, FIXTURE LEGEND AND |
| | LIGHTING POWER DENSITIES. |
| | PLEASE SEE THE WATTAGE ON FIXTURES |
| | PLEASE SEE THE AMOUNT OF FIXTURES |
| | PLEASE SEE THE TYPE OF FIXTURES |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | |
| | 2) NOTE: PLEASE SEE AS RISER HAS BEEN REVISED, PLEASE |
| | SEE NO FLOATING NEUTRAL INDICATED ON RISER AT NEW |
| | METER. 250.6 |
| | |
| | 3) NOTE: PLEASE INDICATE THE AIC RATING FOR THE NEW |
| | MAIN. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |