| Date |
Text |
| 2007-04-25 18:29:28 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | WEST PALM BEACH CITY CODE |
| | |
| | ***FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT P-1 THE SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. VENTS ARE REQUIRED FOR THE MOP SINK, |
| | THE WOMEN'S TOILET ROOM LAV, AND THE 2ND HAND SINK. |
| | SECTION 901.2.1. THE 3RD HAND SINK REQUIRED BY DBPR |
| | REVIEW NOTES SHALL BE SHOWN ON THE RISER DIAGRAM. |
| | SECTION 106.1.1.--THE DISHWASHER SHALL CONNECT TO |
| | SANITARY, NOT THE GREASE DRAIN AS SHOWN. MUNICIPAL CODE |
| | SECTION 90-124(7)(B). |
| | ****RESPONSE NOTED, BUT THE SANITARY RISER DIAGRAM DOES |
| | NOT SHOW THE ADDED FLOOR SINK FOR THE DISHWASHER. ALSO |
| | A VENT IS REQUIRED WITHIN 10 FEET OF THE TRAP PER TABLE |
| | 906.1.--THE GREASE RISER DIAGRAM STILL SHOWS THE |
| | FLOOR SINK FOR THE DISHWASHER AND DOES NOT SHOW THE |
| | HAND SINK ADDED. PLEASE CORRELATE THE FLOOR PLAN AND |
| | RISER DIAGRAM INFORMATION. |
| | |
| | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" |
| | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED |
| | AND STAMPED BY DBPR PLAN REVIEW. |
| | ****NO RESPONSE, NOT ADDRESSED.--NOW THE REQUIRED |
| | SHEETS THAT WERE STAMPED BY DBPR HAVE BEEN REMOVED. |
| | EACH SET OF PLANS SHALL HAVE A DBPR STAMPED SHEET WITH |
| | THE TWO PAGE WORKSHEETS ATTACHED. |
| | |
| | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, |
| | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE |
| | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. |
| | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. #3434. |
| | ****RESPONSE NOTED. SUBJECT NOT ADDRESS. I WILL TRY TO |
| | GET THE INFORMATION FROM THE ENVIRONMENTAL COMPLIANCE |
| | MANAGER. |
| | |
| | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, NOT ADDRESSED |
| | |
| | C. N/A |
| | D. N/A |
| | E. OK |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |