| Date |
Text |
| 2007-02-08 14:13:56 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | WEST PALM BEACH CITY CODE |
| | |
| | 1. COVER SHEET INDICATES THAT THE KITCHEN AREA IS |
| | 1,313SF, THE DINING UNCONCENTRATED 210SF, AND THE |
| | DINING FIXED SEATING 107SF. THIS TOTALS 1,630SF. THE |
| | FLOOR PLAN SHT A-1 AND THE APPLICATION INDICATE A GROSS |
| | SF OF 3,511SF, WHICH LEAVES 1,941 SF UNACCOUNTED FOR. |
| | PLEASE CLARIFY. PLEASE CONFIRM THE MINIMUM REQUIREMENTS |
| | PER TABLES 1004.1.2 AND 403.1. INDICATE ALL |
| | OCCUPANCIES, (STORAGE, BUSINESS ETC.), THAT MAY BE |
| | LOCATED WITHIN THE RESTURANT. PLEASE KEEP IN MIND THAT |
| | POTTY PARITY MAY BE REQUIRED DEPENDING ON THE NUMBER OF |
| | WATER CLOSETS/URINALS REQUIRED IN THE MEN'S TOILET |
| | ROOM. SECTION 403.1.1. |
| | |
| | 2. SHT A-3 (49 SEATS NOT COUNTING THE BENCH SEATING). |
| | INDICATE THE LENGTH OF EACH BENCH. PER SECTION 1004.7, |
| | THE OCCUPANT LOAD OF SEATING BOOTHS SHALL BE BASED ON |
| | ONE PERSON FOR EACH 24 INCHES OF BOOTH SEAT LENGTH |
| | MEASURED AT THE BACKREST OF THE SEATING BOOTH. |
| | |
| | 3. SHT P-1 THE SANITARY RISER DIAGRAM DOES NOT MEET |
| | CODE REQUIREMENTS. VENTS ARE REQUIRED FOR THE MOP SINK, |
| | THE WOMEN'S TOILET ROOM LAV, AND THE 2ND HAND SINK. |
| | SECTION 901.2.1. THE 3RD HAND SINK REQUIRED BY DBPR |
| | REVIEW NOTES SHALL BE SHOWN ON THE RISER DIAGRAM. |
| | SECTION 106.1.1.--THE DISHWASHER SHALL CONNECT TO |
| | SANITARY, NOT THE GREASE DRAIN AS SHOWN. MUNICIPAL CODE |
| | SECTION 90-124(7)(B). |
| | |
| | 4. 1 COPY OF THE TWO PAGE "SPECIFICATION WORKSHEETS" |
| | SHALL BE ATTACHED TO EACH SET OF PLANS STAMPED REVIEWED |
| | AND STAMPED BY DBPR PLAN REVIEW. |
| | |
| | 5. THE EXISTING GREASE INTERCEPTOR SHALL BE INSPECTED, |
| | APPROVED, AND SIZED BY ENVIRONMENTAL COMPLIANCE. PLEASE |
| | CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE MANAGER. |
| | (561) 822-2271, FAX (561) 722-2279, OR E-MAIL |
| | [email protected]. WASTE ORD. #3434. |
| | |
| | 6. THE FOLLOWING INFORMATION IS REQUIRED FOR THE |
| | SEPARATE GAS PERMIT: |
| | |
| | A. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | C. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | D. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT |
| | ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD |
| | COLLECT. (SEE THE W/H). SECTION 408.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |