| Plan Review Notes For Permit 07010448 |
| Permit Number |
07010448 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-02-08 14:15:04 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARATE GAS PERMIT: | | | | | | A. TYPE OF GAS, (LP OR NATURAL). | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | C. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | D. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | E. WHERE WET GAS EXISTS, A DRIP SHALL BE PROVIDED AT | | | ANY POINT IN THE LINE OF PIPE WHERE CONDENSATE COULD | | | COLLECT. (SEE THE W/H). SECTION 408.2. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|