| 2007-02-20 14:36:58 | *****DENIED***** |
| | |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FORM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 03.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF |
| | NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE |
| | OR HINDER WITH ACCESS TO OR EXIT FROM THE STRUCTURE OR |
| | THE VICINITY OF THE STRUCTURE (INCLUDING FIRE LANES). |
| | |
| | 04.THE COMPLETE ADDRESS , INCLUDING THE TENANT SPACE |
| | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED |
| | PLAN SHEET. |
| | |
| | 05.ON THE APPROPIATE EXTERIOR ELEVATION DETAIL, |
| | DISPLAY THE TENANT SPACE NUMBER FOR THIS SITE.AS PER |
| | WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS |
| | THAN 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 06.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES |
| | THE TRAVEL DISTANCE TO THE EXIT(S). |
| | |
| | 07.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR |
| | THIS TENANT SPACE.IF THE SPRINKLER SYSTEM IS MODIFIED |
| | DUE TO THE SCOPE OF WORK, SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED. |
| | |
| | 08.THE INTERIOR WALL AND CEILING FINISH MATERIALS |
| | SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS |
| | HAVING OCCUPANT LOADS OF 300 OR FEWER.PLEASE |
| | SPECIFY. |
| | |
| | 09.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE |
| | WITH NFPA 96.SEPARATE PLANS SND PERMIT WILL BE |
| | REQUIRED FOR THE COOKING HOOD INSTALLATIN AND THE |
| | ASSOCIATED SUPPRESSION SYSTEM. |
| | |
| | 10.SMOKE DUCT DETECTORS, AS INDICATED ON SHEET M1, |
| | SHALL INITIATE A GENERAL FIRE ALARM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS |
| | ADDRESSED. |
| | |
| | |