| 2007-01-28 18:21:36 | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE KNOW AS PROJECT WAS APPLIED FOR PERMIT |
| | AFTER DECEMBER 8TH, 2006 THE FOLLOWING CODES FOR DESIGN |
| | AND AS REFERENCED ON PLANS HAVE CHANGED. |
| | PLEASE KNOW THE STATE HAS NOW ADOPTED THE 2006 |
| | REVISIONS TO THE 2004 FBC WHICH HAS CHANGES FOR |
| | BUILDING, MECHANICAL, PLUMBING AND CHANGES FOR CHAPTER |
| | 13 WHICH WILL AFFECT THE ELECTRICAL PLANS. |
| | PLEASE ALSO KNOW THE ELECTRICAL CODE NOT ADOPTED AS OF |
| | 12/8/06 IS THE 2005 NFPA-70 (NEC). |
| | PLEASE BE SURE THE ARCHITECTURAL PLANS AND MEP'S ARE |
| | UPDATED WITH CODE REFERENCES. |
| | |
| | PLEASE ADJUST PLANS, DESIGNS AND PLEASE BE SURE TO SEE |
| | ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THE |
| | PLANS. PLEASE SEE THE CALCULATIONS INDICATE THE |
| | CONTROLS FOR LIGHTING AS MANUAL. |
| | PLEASE ALSO PROVIDE PERFORMANCE CALCULATIONS PER |
| | 13-415.2. |
| | PLEASE VERIFY THE METHOD WHICH IS BEING USED. PLEASE |
| | SEE THIS IS SUBMITTED AS METHOD *A*WILL THIS |
| | INCORPORATE ALL AREAS? |
| | ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT |
| | SEALED BY THE DESIGNER OF RECORD AS REQUIRED. |
| | 13-103.1.1.1 |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PANEL *A*. PLEASE |
| | SEE ONE SHOWS 600A MLO AND THE OTHER ON RISER AS 400A |
| | MLO. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THAT IF ANY FIRE ALARM SYSTEMS ARE |
| | REQUIRED AND INSTALLED. PLEASE INDICATE ALL THE MINIMUM |
| | LEVELS FOR THESE DEVICES ON PLANS. PLEASE ALSO INDICATE |
| | THE LOCATIONS. PLEASE SEE KNOW IF APPLICABLE, THESE |
| | WILL BE REQUIREDTO BE SHOWN ON BASE PLANS EVEN THOUGH |
| | THESE SYSTEMS WILL BE UNDER SEPARATE PERMITS AND PLANS |
| | AT A LATER DATE. PLEASE SEE THE 2004 FBC 11-4.28.1,.2 |
| | AND .3(4) FOR MINIMUM LEVELS TO BE INDICATED. |
| | |
| | 5) NOTE: PLEASE CLARIFY ELECTRICAL SHUNT FOR ELECTRICAL |
| | DEVICES AND/OR EQUIPMENT UNDER HOOD. PLEASE SEE |
| | NFPA-96. |
| | |
| | 6) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING 600AMP |
| | MAIN SERVICE WHICH THIS NEW SERVICE IS BEING TAPPED |
| | FROM GUTTER. |
| | PLEASE INDICATE. 220, 215.5, 220.3, 220.12, |
| | 220.14,220.42 220.87 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL KIT* |
| | REQUIRED AT THE METER CAN. THIS CAN BE DONE BY A NOTE |
| | ON PLANS. 250.6, 250.24B. |
| | |
| | 8) NOTE: PLEASE PROVIDE A LOAD SUMMARY ON HOW LOADS FOR |
| | SHOW WINDOWS WERE DERIVED. (X-AMOUNT OF FEET TIMES |
| | 200VQA PER FT =Y). PLEASE PROVIDE IN THE SUMMARY HOW |
| | RECEPTACLE LOAD WAS DERIVED. (X AMOUNT OF DEVICES TIMES |
| | 180VA=?). |
| | PLEASE CLARIFY WHERE THE CONTINUOUS LOAD WAS DERIVED. |
| | THIS CAN BE DONE WITH THE LIGHTING LOADS. |
| | 220.43, 220.44 ETC. |
| | FBC 106.1.2, 106.3.5.1.2. |
| | |
| | 9) NOTE: PLEASE CLARIFY CONTROL DEVICES BEING SHOWN FOR |
| | HALLWAY/EGRESS LIGHTS AS A S/D. IS THIS A DIMMER? |
| | PLEASE CLARIFY HOW THE MINIMUM LIGHTING LEVELS FOR |
| | EGRESS UNDER NORMAL CONDITIONS WILL BE MET BY PLACING A |
| | DIMMER ON THESE LIGHTS TO MEET LS 101 7.8,7.9. |
| | * PLEASE ALSO SEE THESE DEVICE IS LISTED WITH PART OF |
| | THE CONTROL DEVICES FOR AUTOMATED SHUT OFF OF LIGHTS. |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | |
| | 10) NOTE: PLEASE SEE ALL SWITCHES ARE BEING SHOWN AS |
| | PASSIVE INFRARED FOR LIGHTING CONTROL WHICH IS OK; |
| | HOWEVER PLEASE SEE NOTE ABOVE FOR EGRESS AND PLEASE |
| | CLARIFY HOW COVERAGE WILL BE MET FOR EGRESS AND NORMAL |
| | OPERATION AS MANY OF THE DEVICES ARE BEING LOCATED AT |
| | ONE LOCATION ON A WALL IN KITCHEN AREA. PLEASE SEE |
| | DEVICES WHICH ARE IN INDIVIDUAL ROOMS LIKE THE |
| | BATHROOMS WHICH CONTAIN FLOOR TO CEILING HEIGHT |
| | PARTITIONS IS OK, HOWEVER THE COVERAGE FOR OVERRIDING |
| | DURING NORMAL BUSINESS HOURS SEEMS LIKE IT WILL NOT |
| | PROVIDE THE NEEDED CONTROL FOR LIGHTING AS SHOWN. |
| | PLEASE SEE MEANS TO OVER RIDER LIGHTING IS ALSO |
| | REQUIRED TO BE AT MEANS OF INGRESS INTO AREA/SPACE. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | PLEASE CALL TO GO OVER SCENARIO AS SHOWN. |
| | |
| | 10) NOTE: PLEASE SEE THE *OR* OPTION FOR FEEDERS FROM |
| | THE METER TO PANEL *A* WHICH IS SHOWING A 1/0 EQUIPMENT |
| | GROUNDING CONDUCTOR FOR 400AMPS. THIS IS ONLY BEING |
| | NOTED AND DOES NOT CREATE ANY CODE COMMENT. |
| | |
| | 11) NOTE: PLEASE SEE PLANS MENTIONS EXTERIOR LIGHTING |
| | IS BY LANDLORD, IF THIS IS THE CASE PLEASE REMOVE FROM |
| | PLANS. PLEASE SEE THE LIGHTING AS SHOWN ON PLANS MAY BE |
| | DONE AS PART OF THIS BUILD OUT. |
| | PLEASE CLARIFY. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | |
| | 12) NOTE: PLEASE BE SURE TO INCLUDE THE UNIT/SUITE |
| | NUMBER ON PLANS FOR LOCATION OF SCOPE OF WORK. THE |
| | PERMIT APPLICAITON AND ADDRESS OF SUITE/UNIT APPLIED |
| | FOR IN OUR SYSTEM INDICATES SUITE 801. |
| | FAC 61G1-16.004 |
| | |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |