| 2007-03-04 07:55:53 | *** UNSAT 2ND REVIEW** |
| | |
| | * PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL NEED |
| | TO BE ADDRESSED. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO, |
| | PLEASE SEE THAT THE SCOPE OF WORK SHALL INCLUDE ALL |
| | LABOR AND MATERIALS EVEN IF EQUIPMENT IS OWNER |
| | SUPPLIED. THE SCOPE OF WORK AND MATERIALS/EQUIPMENT AS |
| | SHOWN WILL BE ASSESSED VALUES PER TABLES IN EVALUATION |
| | BOOKS ADOPTED BY THE FBC. PLEASE SEE THE SCOPE SEEMS |
| | LOW. PLEASE ADJUST. |
| | FBC 108.3 |
| | |
| | 3) NOTE: NO,THE NOTES ADDED ON PLANS FOR ONE OF THE |
| | SUB ELECTRICAL ROOMS TO ADD SIGNAGE IS NOT ALL THAT IS |
| | REQUIRED TO BE SHOWN ON PLANS. TRAVEL DISTANCE AND |
| | LOCATION OF ALL DISCONNECTING MEANS FOR POWER TO THIS |
| | STRUCTURE WILL BE DETERMINED BY THIS OFFICE FOR THE |
| | LIFE SAFETY ASPECT OF TRAVEL DISTANCE, TIME ETC. |
| | PLEASE CLARIFY THE LOCATION OF EXISTING MAIN ELECTRICAL |
| | ROOM. PLEASE SEE THE REQUIRED MEANS OF DISCONNECT FOR |
| | THE FEED FROM THE GENERATOR COULD NOT BE LOCATED. |
| | PLEASE SEE SIGNAGE ETC. |
| | 225.31-225.39, 701OR 702 |
| | |
| | 4) NOTE: NO, A RESPONSE LETTER OR INFORMATION WAS NOT |
| | PROVIDED TO SHOW OTHER WISE. |
| | PLEASE SUBMIT INFORMATION AS PREVIOUSLY REQUESTED. |
| | PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA STATUES |
| | WHICH NOW REQUIRES BACK UP POWER FOR THESE SYSTEMS AS |
| | LEGALLY REQUIRED. IF THIS IS THE CASE AS STATED, WOULD |
| | NOT THE LEGALLY REQUIRED BACK UP BE PERMANENT? |
| | PLEASE SEE NFPA-110,NFPA-70 701 |
| | |
| | 5) NOTE: NO, PLEASE SEE THE PLANS STILL CONTAIN THE |
| | SAME NOTE AND THE INFORMATION AS REQUIRED AND REQUESTED |
| | IS NOT ON PLANS. THIS LOAD INFORMATION IS REQUIRED AT |
| | THIS TIME AND TO BE ON PLANS AND THE RESPONSIBILITY OF |
| | THE DESIGNER OF RECORD. |
| | PLEASE SUBMIT THE LOADS ON THE EXISTING EQUIPMENT |
| | WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE WHICH |
| | MENTIONS THAT THE CONTRACTOR SHALL PROVIDE READINGS, |
| | LOAD TESTING ETC IS NOT PERMITTED. THIS MUST BE DONE AT |
| | THIS TIME BEFORE ISSUANCE PERMIT AND THIS INFORMATION |
| | MUST BE PART OF THE DESIGN AND STATED ON PLANS. |
| | 220.87. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | NOTES 6-9 ARE OK OR NOT APPLICABLE FOR THIS REVIEWER AT |
| | THIS TIME. |
| | |
| | ** PLEASE KNOW THAT A TYPED WRITTEN RESPONSE EXPLAINING |
| | ANY OF THE COMMENTS OR HOW THE COMMENT WAS ADDRESSED |
| | WOULD HELP IN THE REVIEW PROCESS. |
| | PLEASE KNOW THAT ALL DOCUMENTATION SHALL BEAR THE NAME, |
| | SIGNATURE AND SEAL FROM THE DESIGNER OF RECORD. |
| | FS 471.023, FAC 61G15-23.002 |
| | |
| | **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY |
| | COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |