Plan Review Notes
Plan Review Notes For Permit 07010435
Permit Number 07010435
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-04 07:55:53*** UNSAT 2ND REVIEW**
  
 * PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL NEED
 TO BE ADDRESSED.
  
 1) NOTE: OK.
  
 2) NOTE: NO,
 PLEASE SEE THAT THE SCOPE OF WORK SHALL INCLUDE ALL
 LABOR AND MATERIALS EVEN IF EQUIPMENT IS OWNER
 SUPPLIED. THE SCOPE OF WORK AND MATERIALS/EQUIPMENT AS
 SHOWN WILL BE ASSESSED VALUES PER TABLES IN EVALUATION
 BOOKS ADOPTED BY THE FBC. PLEASE SEE THE SCOPE SEEMS
 LOW. PLEASE ADJUST.
 FBC 108.3
  
 3) NOTE: NO,THE NOTES ADDED ON PLANS FOR ONE OF THE
 SUB ELECTRICAL ROOMS TO ADD SIGNAGE IS NOT ALL THAT IS
 REQUIRED TO BE SHOWN ON PLANS. TRAVEL DISTANCE AND
 LOCATION OF ALL DISCONNECTING MEANS FOR POWER TO THIS
 STRUCTURE WILL BE DETERMINED BY THIS OFFICE FOR THE
 LIFE SAFETY ASPECT OF TRAVEL DISTANCE, TIME ETC.
 PLEASE CLARIFY THE LOCATION OF EXISTING MAIN ELECTRICAL
 ROOM. PLEASE SEE THE REQUIRED MEANS OF DISCONNECT FOR
 THE FEED FROM THE GENERATOR COULD NOT BE LOCATED.
 PLEASE SEE SIGNAGE ETC.
 225.31-225.39, 701OR 702
  
 4) NOTE: NO, A RESPONSE LETTER OR INFORMATION WAS NOT
 PROVIDED TO SHOW OTHER WISE.
 PLEASE SUBMIT INFORMATION AS PREVIOUSLY REQUESTED.
 PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA STATUES
 WHICH NOW REQUIRES BACK UP POWER FOR THESE SYSTEMS AS
 LEGALLY REQUIRED. IF THIS IS THE CASE AS STATED, WOULD
 NOT THE LEGALLY REQUIRED BACK UP BE PERMANENT?
 PLEASE SEE NFPA-110,NFPA-70 701
  
 5) NOTE: NO, PLEASE SEE THE PLANS STILL CONTAIN THE
 SAME NOTE AND THE INFORMATION AS REQUIRED AND REQUESTED
 IS NOT ON PLANS. THIS LOAD INFORMATION IS REQUIRED AT
 THIS TIME AND TO BE ON PLANS AND THE RESPONSIBILITY OF
 THE DESIGNER OF RECORD.
 PLEASE SUBMIT THE LOADS ON THE EXISTING EQUIPMENT
 WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE WHICH
 MENTIONS THAT THE CONTRACTOR SHALL PROVIDE READINGS,
 LOAD TESTING ETC IS NOT PERMITTED. THIS MUST BE DONE AT
 THIS TIME BEFORE ISSUANCE PERMIT AND THIS INFORMATION
 MUST BE PART OF THE DESIGN AND STATED ON PLANS.
 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 NOTES 6-9 ARE OK OR NOT APPLICABLE FOR THIS REVIEWER AT
 THIS TIME.
  
 ** PLEASE KNOW THAT A TYPED WRITTEN RESPONSE EXPLAINING
 ANY OF THE COMMENTS OR HOW THE COMMENT WAS ADDRESSED
 WOULD HELP IN THE REVIEW PROCESS.
 PLEASE KNOW THAT ALL DOCUMENTATION SHALL BEAR THE NAME,
 SIGNATURE AND SEAL FROM THE DESIGNER OF RECORD.
 FS 471.023, FAC 61G15-23.002
  
 **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY
 COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]