2007-03-29 10:59:40PERMIT: 07010435
 ADD: 4920 LORING DR
 CONT: DYNAMIC SOUTH, INC
 TEL: (239)283-3338
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) 2ND REQUEST,SHEET A-3A PLANS INDICATE A ENLARGED
 EQUIPMENT PLANS, PLANS DO NOT INDICATE WHERE THE
 BATTERY CABINETS ARE LOCATED? STRUCTURAL PLAN ALSO
 INDICATES
 2900 LBS EACH, HOW MANY BATTERY CABINETS ARE THERE?
  
 3B) 2ND REQUEST,PLEASE PROVIDE WHAT OCCUPANCY
 CLASSIFICATION THIS PENTHOUSE IS CLASSIFIED AS?
 TABLE302.1.1
 307.9 EXCEPTIONS (11)
 STATIONARY BATTERIES UTILIZED FOR FACILITY EMERGENCY
 POWER, UNINTERRUPTED POWER SUPPLY OR TELECOMMUNICATION
 FACILITIES PROVIDED THAT THE BATTERIES ARE PROVIDED
 WITH SAFETY VENTING CAPS AND VENTILATION IS PROVIDED IN
 ACCORDANCE WITH THE F LORIDA BUILDING CODE, MECHANICAL
 .
  
 4) 2ND REQUEST,WHAT TYPE OCCUPANCY IS BELOW THIS
 LEVEL PROVIDE THE RATED ASSEMBLY FOR THE FLOOR CEILING
 ASSEMBLY.
  
 5A)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5B) 2ND REQUEST,WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 C) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 LOUVERED DOOR
 WALL LOUVER - PROVIDE THE FLORIDA COVERSHEET AND
 ASSOCIATED NOA.
  
 6) 2ND REQUEST, PLEASE PROVIDE THE POSITIVE AND
 NEGATIVE PRESSURES FOR THE NEW OPENINGS
 NOTE > 60'-0" ABOVE GRADE NEEDS TO REFLECT DESIGNED TO
 ASCE 7-02,
 1609.1.1
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]