| Date |
Text |
| 2007-01-21 11:50:22 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE STATE ALL OF THE FOLLOWING RELEVANT |
| | CODES ON PLANS. PLEASE SEE AS OF DECEMBER 8TH, 2006 THE |
| | STATE OF FLORIDA ADOPTED THE 2005 NFPA-70. PLEASE SEE |
| | THE PLANS NOTES A 2003 NEC. PLEASE KNOW THERE WAS THE |
| | 2002. |
| | PLEASE ALSO LIST THE 2002 NFPA-72 AND THE 2003 |
| | NFPA-101. |
| | |
| | 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL BE SHOWN FOR ALL LABOR AND MATERIALS EVEN IF |
| | EQUIPMENT IS OWNER SUPPLIED.. |
| | FBC 108.3 |
| | |
| | 3) NOTE: PLEASE CLARIFY THE LOCATION OF EXISTING MAIN |
| | ELECTRICAL ROOM. PLEASE SEE THE REQUIRED MEANS OF |
| | DISCONNECT FOR THE FEED FROM THE GENERATOR COULD NOT BE |
| | LOCATED. |
| | PLEASE SEE SIGNAGE ETC. |
| | 225.31-225.39, 701OR 702 |
| | |
| | 4) NOTE: PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA |
| | STATUES WHICH NOW REQUIRES BACK UP POWER FOR THESE |
| | SYSTEMS AS LEGALLY REQUIRED. IF THIS IS THE CASE AS |
| | STATED, WOULD NOT THE LEGALLY REQUIRED BACK UP BE |
| | PERMANENT? |
| | PLEASE SEE NFPA-110,NFPA-70 701 |
| | |
| | 5) NOTE: PLEASE SUBMIT THE LOADS ON THE EXISTING |
| | EQUIPMENT WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE |
| | WHICH MENTIONS THAT THE CONTRACTOR SHALL PROVIDE |
| | READINGS, LOAD TESTING ETC IS NOT PERMITTED. THIS MUST |
| | BE DONE AT THIS TIME BEFORE ISSUANCE PERMIT AND THIS |
| | INFORMATION MUST BE PART OF THE DESIGN AND STATED ON |
| | PLANS. |
| | 220.87. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE BUILDING REVIEW NOTES PERTAINING TO |
| | PRODUCT DATA SUBMITTALS WHICH WERE NOT SUBMITTED WITH |
| | PLANS. |
| | ONLY NOTED. |
| | |
| | 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PANEL/TRANSFER SWITCH. PLEASE BE SURE |
| | THIS CONTAINS A LISTING FROM A NRTL. |
| | 110.3, 90.7, 701.7 |
| | |
| | 8) NOTE: PLEASE CLARIFY AN EQUIPMENT GROUND FROM THE |
| | *6SDL* TO THE EMON METER AND DISCONNECT. PLEASE CLARIFY |
| | AS THE CONDUITS ON SHEETS CONTAINING SOME OF THESE WITH |
| | EQUIPMENT GROUNDING AND SOME DO NOT? |
| | 250.110, 250.24, 250.122 |
| | |
| | 9) NOTE: PLEASE SEE THE ADDRESS DOES NOT CORRELATE WITH |
| | THE APPLIED LOCATION, PLANS AND THE PALM BEACH COUNTY |
| | PROPERTY APPRIASERS. THIS HAS BEEN ROUTED TO THE |
| | ADDRESSING PERSON AND ONCE THE FINAL ADDRESS IS |
| | DETERMINED, PLEASE BE SURE THE PLANS CONTAIN THE ACTAUL |
| | ADDRESS IN THE TITLE BLOCKS. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY |
| | COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |