Plan Review Notes For Permit 07010435
Permit Number 07010435
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-21 11:50:22** UNSAT **
  
 1) NOTE: PLEASE STATE ALL OF THE FOLLOWING RELEVANT
 CODES ON PLANS. PLEASE SEE AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTED THE 2005 NFPA-70. PLEASE SEE
 THE PLANS NOTES A 2003 NEC. PLEASE KNOW THERE WAS THE
 2002.
 PLEASE ALSO LIST THE 2002 NFPA-72 AND THE 2003
 NFPA-101.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL BE SHOWN FOR ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT IS OWNER SUPPLIED..
 FBC 108.3
  
 3) NOTE: PLEASE CLARIFY THE LOCATION OF EXISTING MAIN
 ELECTRICAL ROOM. PLEASE SEE THE REQUIRED MEANS OF
 DISCONNECT FOR THE FEED FROM THE GENERATOR COULD NOT BE
 LOCATED.
 PLEASE SEE SIGNAGE ETC.
 225.31-225.39, 701OR 702
  
 4) NOTE: PLEASE CLARIFY THE REQUIREMENTS UNDER FLORIDA
 STATUES WHICH NOW REQUIRES BACK UP POWER FOR THESE
 SYSTEMS AS LEGALLY REQUIRED. IF THIS IS THE CASE AS
 STATED, WOULD NOT THE LEGALLY REQUIRED BACK UP BE
 PERMANENT?
 PLEASE SEE NFPA-110,NFPA-70 701
  
 5) NOTE: PLEASE SUBMIT THE LOADS ON THE EXISTING
 EQUIPMENT WHICH THE NEW LOADS ARE BEING ADDED. THE NOTE
 WHICH MENTIONS THAT THE CONTRACTOR SHALL PROVIDE
 READINGS, LOAD TESTING ETC IS NOT PERMITTED. THIS MUST
 BE DONE AT THIS TIME BEFORE ISSUANCE PERMIT AND THIS
 INFORMATION MUST BE PART OF THE DESIGN AND STATED ON
 PLANS.
 220.87.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE BUILDING REVIEW NOTES PERTAINING TO
 PRODUCT DATA SUBMITTALS WHICH WERE NOT SUBMITTED WITH
 PLANS.
 ONLY NOTED.
  
 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PANEL/TRANSFER SWITCH. PLEASE BE SURE
 THIS CONTAINS A LISTING FROM A NRTL.
 110.3, 90.7, 701.7
  
 8) NOTE: PLEASE CLARIFY AN EQUIPMENT GROUND FROM THE
 *6SDL* TO THE EMON METER AND DISCONNECT. PLEASE CLARIFY
 AS THE CONDUITS ON SHEETS CONTAINING SOME OF THESE WITH
 EQUIPMENT GROUNDING AND SOME DO NOT?
 250.110, 250.24, 250.122
  
 9) NOTE: PLEASE SEE THE ADDRESS DOES NOT CORRELATE WITH
 THE APPLIED LOCATION, PLANS AND THE PALM BEACH COUNTY
 PROPERTY APPRIASERS. THIS HAS BEEN ROUTED TO THE
 ADDRESSING PERSON AND ONCE THE FINAL ADDRESS IS
 DETERMINED, PLEASE BE SURE THE PLANS CONTAIN THE ACTAUL
 ADDRESS IN THE TITLE BLOCKS.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 **PLEASE CLARIFY AND SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS, OR IF THERE ANY
 COMMENTS ON THE NOTES TYPE ON REVIEW, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]