| 2007-06-08 11:52:15 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). |
| | |
| | 2) NOTE: PLEASE SEE RISER NOW INDICATES 2/0 CONDUCTORS |
| | BEING FED TO A 60A BREAKER. PLEASE KNOW THIS IS NOT |
| | POSSIBLE AS THIS SIZE CONDUCTOR WILL NOT FIT INTO THE |
| | LUGS.225.31-225.39 FOR DISCONNECTING MEANS FOR THE |
| | CIRCUIT(S) TO THIS DETACHED STRUCTURE. PLEASE INDICATE |
| | WHERE THE FEED IS COMING FROM AND HOW IT IS GETTING TO |
| | THIS NEW LOCATION. |
| | PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS |
| | ETC. |
| | 240.4, 310.16, 408.4, 300.5 ETC |
| | |
| | 3) NOTE: PLEASE SEE NO PANEL SCHEDULE FOR CIRCUITS AT |
| | THE DETACHED BUILDING WAS SUBMITTED. |
| | PLEASE SEE 408.4. |
| | |
| | 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE |
| | CONNECTION. PLEASE SEE 250.32 AND 250.50 |
| | |
| | 5) NOTE: PLEASE SEE RISER DOES NOT INDICATE ANY OCP AT |
| | THE MAIN EXISTING PANEL AS SHOWN TO FEED NEW PANEL. |
| | PLEASE ALSO CLARIFY WHAT IS BEING SHOWN AS TWO CONDUITS |
| | FROM THE MAIN EXISTING PANEL TO NEW PANEL. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | PLEASE SEE 408.4, 240.4, 310.16. |
| | |
| | 6) NOTE: PLEASE SEE THE ADDRESS FOR SAID PROJECT HAS |
| | NOW CHANGED, PLEASE BE SURE TO REVISED PERMIT |
| | APPLICATION AND PLAN TITLE BLOCKS TO NEW ADDRESS. |
| | FAC 61G1-16.004 |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |