| 2007-01-14 17:11:29 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL CODES SHALL BE STATED ON |
| | PLANS FOR THE DESIGNS WHICH THEY ARE UNDER. |
| | PLEASE KNOW AS THIS WAS SUBMITTED FOR PERMIT AFTER |
| | DECEMBER 8TH, 2006, THE FOLLOWING NEW CODES ARE |
| | RELEVANT. |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70 |
| | (NEC). |
| | |
| | 2) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING |
| | MEANS FOR THE CIRCUIT(S) TO THIS DETACHED STRUCTURE. |
| | PLEASE INDICATE WHERE THE FEED IS COMING FROM AND HOW |
| | IT IS GETTING TO THIS NEW LOCATION. |
| | PLEASE INDICATE THE SIZE OF THE CIRCUITS, CONDUCTORS |
| | ETC. |
| | 240.4, 310.16, 408.4, 300.5 ETC |
| | |
| | 3) NOTE: PLEASE SEE RECEPTACLE AT THIS BUILDING IS |
| | REQUIRED TO BE GFI PROTECTED. |
| | 210.8(B)(1) & (4). |
| | |
| | 4) NOTE: PLEASE ALSO THE MISSING GROUNDING ELECTRODE |
| | CONNECTION. PLEASE SEE 250.32 |
| | |
| | 5) NOTE: PLEASE SEE EVEN THOUGH NOT REQUIRED THE THIRD |
| | SET OF PLANS SUBMITTED WERE NOT SIGNED, DATED OR |
| | SEALED. IF THE THIRD SET WAS SUBMITTED TO HAVE AN EXTRA |
| | COPY STAMPED, PLEASE BE SURE THE DESIGNER OF RECORD |
| | SIGNS, DATES AND SEALS LIKE THE OTHER SETS. |
| | *THIS IS ONLY NOTED AS THE TWO REQUIRED ARE OK. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |